Liebert XDP160RA, XDP160RM High Refrigerant Temp Enable ALM, LOW Refrigerant Temp Enable ALM

Page 59

Liebert iCOM Control—Firmware Version XP1.00.010.STD

Figure 57 Set Alarms screen, page 4 of 7

 

 

 

 

 

 

 

 

 

 

S236

PASSWORD (Actual Level 0)

 

????

S237

 

 

DELAY

EN-DIS TYPE

S238

HIGH REFRIGERANT TEMP

30

ENABLE ALM

S239

LOW REFRIGERANT TEMP

30

ENABLE ALM

S240

SUPPLY REFRIGERANT SENSOR

ENABLE ALM

S241

LOSS OF FLOW PUMP 1

 

ENABLE ALM

S242

LOSS OF FLOW PUMP 2

 

ENABLE ALM

S243

PUMP SHORT CYCLE

 

ENABLE ALM

S244

 

 

 

 

S245

 

 

 

 

S246

 

 

 

 

S247

CONTROL VALVE FAILURE

 

ENABLE ALM

S248

 

 

 

 

 

 

for next/previous unit

to select parameter

then

to change parameter

 

to confirm

HIGH REFRIGERANT TEMP—Enables or disables the High Refrigerant Temp event, which occurs when the reading from supply refrigerant temperature sensor is above the user-specified alarm setpoint. Sets how the event is reported: as an alarm, a warning or a message. Specifies how long the control waits before reporting the event.

LOW REFRIGERANT TEMP—Enables or disables the Low Refrigerant Temp event, which occurs when the reading from supply refrigerant temperature sensor is below the user-specified alarm setpoint. Sets how the event is reported: as an alarm, a warning or a message. Specifies how long the control waits before reporting the event.

SUPPLY REFRIGERANT SENSOR—Enables or disables the Supply Refrigerant Sensor event, which occurs when the control no longer senses a signal from the Supply Refrigerant Sensor. Sets how the event is reported: as an alarm, a warning or a message. Specifies how long the control waits before reporting the event.

LOSS OF FLOW PUMP 1—Enables or disables the Loss of Flow Pump 1 event, which occurs when Pump 1 is commanded to run and the differential pressure switch does not sense differential pressure. Sets how the event is reported: as an alarm, a warning or a message. Specifies how long the control waits before reporting the event.

LOSS OF FLOW PUMP 2—Enables or disables the Loss of Flow Pump 2 event, which occurs when Pump 2 is commanded to run and the differential pressure switch does not sense differential pressure. Sets how the event is reported: as an alarm, a warning or a message. Specifies how long the control waits before reporting the event.

PUMP SHORT CYCLE—Enables or disables the Pump Short Cycle event, which occurs when flow is not established by either pump for 30 minutes. Sets how the event is reported: as an alarm, a warning or a message. Specifies how long the control waits before reporting the event.

CONTROL VALVE FAILURE—Enables or disables the Control Valve Failure event, which occurs when the chilled water control valve has been commanded by the control to open or close and no change is detected by the valve position signal. Sets how the event is reported: as an alarm, a warning or a message. Specifies how long the control waits before reporting the event.

53

Image 59
Contents Liebert XDP with Liebert iCOM Control Page Table of Contents Start the Liebert XDP with Liebert Icom Alarm Descriptions and SolutionsSpecifications Figures Tables Important Safety Instructions = 460V-3ph-60Hz Place holder Example XDP160RAPumping Unit Redundancy Place holder Revision Level Liebert Minimum Load General Product InformationEquipment Inspection Product/System DescriptionHandling the Liebert XDP While it is on Skid and Packaged Equipment HandlingUnpacking the Liebert XDP Removing the Unit from the Skid Using a ForkliftUse a forklift to remove the Liebert XDP from the skid Removing the Unit from the Skid using RiggingSpreader Bars Bracket Moving the Liebert XDP Using Piano JacksSecuring the Liebert XDP to piano jacks Removing the Unit from the Piano JacksPositioning the Liebert XDP Liebert XDP dimensionsMechanical Considerations Model Pipe Connection Point 50/60 Hz Electrical ConsiderationsUnit piping outlet connection sizes, inches, OD Cu Front view of Liebert XDP and electrical enclosure Connecting High-Voltage CablesHigh voltage connections-60Hz High voltage connections-50Hz Extra Low Voltage ELV ConnectionsConnecting the remote temperature/humidity sensors DIP switch and jumper settings DIP Switch and Jumper Settings for Remote SensorsLiebert XDP extra low voltage field connections points Field Connections-Optional for All UnitsSuggested remote sensor placement Remote Sensor Installation-Proper PlacementSupply, return pipe sizes for refrigerant loop European Union Fluorinated Greenhouse Gas RequirementsConnection Sizes Recommended Pipe SizeLiebert XDP Piping Installation MethodsPiping Installation-R-134a Pumped Circuit Liebert XDP Interconnection with Liebert XD Cooling ModulesRequired Number of Open Piping MainsBypass Flow Controller Bypass flow controllers for a Liebert XDP-based systemBypass flow controller arrangement Piping Details-Shutoff/Isolation ValvesFloor Supply Return Liebert Evacuation and Leak Check-R-134a Pumped CircuitInsulation System refrigerant charge for the supply and return mains Filling the Pumped Circuit-R-134aWorksheet to calculate refrigerant charge Calculating Refrigerant Charge-ExampleCalculating refrigerant charge-example Checklist for Proper Installation Escape Key Down Arrow Key Liebert iCOM Components and FunctionsIcon Key Name Function Display Lamp IndicatorsKeyboard icons and functions Unit Sensor a Sensor B Pump Operation Roo m Data Room Data Accessing Menus and Settings Viewing DataNavigating Through the Liebert iCOM Display ACK High Chilled Water Temp Cooling Module OverviewEntering the password Entering the PasswordEnglish US Changing Liebert iCOM’s Display SettingsChanging Operational Settings Highlight the setting to be changed by pressing EnterLiebert iCOM User Menu Icons and Legend Graphical Data RecordLiebert XDP User Menu screen Event Log Liebert iCOM User Menu ScreensSpare Parts SET Alarms page 1 Sensor Data screen, page 1 Sensor Data screen, page 2 U401 U402 XDV8SK OnlineXDO20SK 20 KW XDH32SKSettings Liebert iCOM Service Menu Icons and LegendSetpoints Maintenance Diagnostics Set Alarms Service ModeLiebert XDP Service Menu screen Liebert iCOM Service Menu ScreensLiebert iCOM Control-Firmware Version XP1.00.010.STD Maintenance-Basic Settings screen, page 1 Maintenance-Pump 1 Settings screen, page 2 Maintenance-Pump 2 Settings screen, page 3 Diagnostics/Service Mode screen, page 1 Manual Mode Control Type-Not currently used Diagnostics/Service Mode screen, page 5 Set Alarms screen, page 1 Set Alarms screen, page 2 High Temp Sensor B Enable ALM Delay EN-DIS TypeHigh Temp Sensor a Enable ALM LOW Temp Sensor a Enable ALMLoss of Flow Pump Enable ALM High Refrigerant Temp Enable ALMLOW Refrigerant Temp Enable ALM Supply Refrigerant Sensor Enable ALMSmoke Detected Enable ALM Condensation Detected Enable ALMFAN Failure Enable ALM Customer Input Enable ALMS601 S612 S801 GBP MACUnit System/Network Setup screen-Unit, page 1S834 S835 S401 Sensor Failure Enable ALM Node ID Delay EN-DIS TypeCondensation Detected Enable Local Module Shutdown Enable ALMNode ID Delay EN-DIS Type Indicator Lights Description Green Red Checklist for Liebert XDP StartupLiebert XDP pump light indicator-208V and 400V units System R-134a liquid level at 160kW load Starting the Liebert XDP with Liebert iCOM ControllerAlarm Descriptions Alarm Descriptions and Solutions Unit Is Off By Pump Short Cycle System Shutdown CausesUnit Is Off By Refrig Sens Fail Unit Is Off By High CW TempSymptom Possible Cause Check or Remedy Troubleshooting the Liebert XDPSee Clogged Filter Dryer and/or Impeller symptom Fluorinated Greenhouse Gas Requirements MaintenanceLiebert XDP160 specifications 2006/42/EC 2004/108/EC 2006/95/EC 97/23/EC Liebert Corporation Dearborn Drive Box Columbus, OHCare Ne tIs t Twor k