THIRD TEMPERATURE TEST:

10.Once the unit has run for 24 hours, perform the third temperature test.

11.Record information and calculate temperature differential in table below for the condenser/back side section under the second test.

Evaporator (Front) Side

Condenser (Back) Side

TEMPERATURE DATA FROM TESTING

Temperature / Test (time)

First (after 5 mins)

Second (after 8 hrs)

Third (after 24 hours)

Inlet Air

 

 

 

 

 

 

 

Outlet Air

 

 

 

 

 

 

 

Differential

 

 

 

(Inlet - Outlet = _; ideally 10°F - 15°F)

 

 

 

Inlet Air

 

 

 

(Ideally < 85°F)

 

 

 

 

 

 

 

Outlet Air

 

 

 

(Ideally < 120°F)

 

 

 

 

 

 

 

Differential

 

 

 

(Inlet - Outlet = _; ideally 10°F - 15°F)

 

 

 

 

 

 

 

TEMPERATURE TESTING LOCATIONS

INLET AIR -- Evaporator (Front) Side*

OUTLET AIR -- Evaporator (Front) Side*

INLET AIR -- Condenser (Back) Side*

OUTLET AIR -- Condenser (Back) Side*

*When measuring outlet air temperature on both sides of the unit (from the circular fans), hold the

thermostat at the outer edges of one of the circular fans.

Page 27

XLT 020111

Image 29
Contents XLT Page Owners Please Note Table of ContentsHow does the WhisperKOOL System Work? What is the WhisperKOOL System?Introduction Contents Customer Warranty RegistrationReceiving & Inspecting the Unit Receiving and Inspecting the UnitQuick Start Guide Wall & Ceiling Framing Preparing the Wine CellarDoor Unobstructed AirflowMounting the Unit Ventilation Ambient Temperature FactorCut horizontal lines from stud to stud Tools NeededMark the horizontal lines with a level Frame the hole with two-by-four supports Cut vertical lines along the inside edge of the studsElectrical Needs InstallationElectrical Outlet Sizing Unit to RoomApplying Insulation Tape Testing UnitLiquid Measuring Thermostat System Attach precut foam tape to the unit’s flangePlacement of Unit Installing ThermostatPower Switch Using the Whisperkool SystemCondensate Evaporator Switch Location of control switchesTo Use the thermostat Liquid Measuring Thermostat SystemOperation PDT JR Operating InstructionsButtons PDT PDT Operating InstructionsMaintenance Maintenance ScheduleNormal Operation Humidity Control85F Max Using the Thermostat ControllerDucting Try this first Troubleshooting GuideAirflow Cool air drops and exits beneath door Door SealAir flows on both sides of the wall Mount WhisperKOOL high in the room Unit MountingThermostat Condensation Power RequirementsIcing Up DrainlineConsumer Care Program Repairing Units Removing RivetsGeneral Inspection Troubleshooting ChecklistUnit is Not Cooling Sufficiently or Not Cooling at All Specific Performance IssuesDo not Exceed 24HRS on Bypass Plug Temperature Differential TestingEvaporator Front Side Condenser Back Side Temperature / Test timeInlet AIR -- Evaporator Front Side Inlet AIR -- Condenser Back SideConclusions Technical Assistance Accessories for Cooling UnitsFive 5 Year Compressor Limited Warranty Installation Terms and ConditionsProduct Installation Requirements Product Warranty Limitations and ExclusionsMaintenance Requirements ModelXLTSerial NumberA Questions or Additional InformationWhisperKOOL WhisperKOOL