THIRD TEMPERATURE TEST:
10.Once the unit has run for 24 hours, perform the third temperature test.
11.Record information and calculate temperature differential in table below for the condenser/back side section under the second test.
Evaporator (Front) Side
Condenser (Back) Side
TEMPERATURE DATA FROM TESTING
Temperature / Test (time) | First (after 5 mins) | Second (after 8 hrs) | Third (after 24 hours) |
Inlet Air |
|
|
|
|
|
|
|
Outlet Air |
|
|
|
|
|
|
|
Differential |
|
|
|
(Inlet - Outlet = _; ideally 10°F - 15°F) |
|
|
|
Inlet Air |
|
|
|
(Ideally < 85°F) |
|
|
|
|
|
|
|
Outlet Air |
|
|
|
(Ideally < 120°F) |
|
|
|
|
|
|
|
Differential |
|
|
|
(Inlet - Outlet = _; ideally 10°F - 15°F) |
|
|
|
|
|
|
|
TEMPERATURE TESTING LOCATIONS
INLET AIR | OUTLET AIR |
INLET AIR | OUTLET AIR |
*When measuring outlet air temperature on both sides of the unit (from the circular fans), hold the
thermostat at the outer edges of one of the circular fans.
Page 27 | XLT 020111 |