WhisperKool XLT 1600 Temperature Differential Testing, Do not Exceed 24HRS on Bypass Plug

Page 28

TEMPERATURE DIFFERENTIAL TESTING

The purpose of this test is to evaluate whether or not your cooling unit is operating correctly by mea- suring the temperatures of both the inside of the cellar and the exhaust side of the unit in the adjoin- ing room. The majority of problems found with cooling units result from inadequate ventilation on the exhaust (back) side of the unit; therefore, taking these measurements is critical in ensuring the optimal performance of the product while minimizing costs of operation.

The WhisperKOOL unit is designed to maintain relative humidity between 50-70%, which is accom- plished by cooling the cellar slowly. You should anticipate an approximate 10 - 15 degree temperature differential between the inlet air temperature and the outlet air temperature on the evaporator (front) side of the unit

When testing the air temperature, please hold the thermometer in the appropriate location for a full minute before recording temperatures so that the thermometer has stabilized. Do not use PDT Probe!

DO NOT EXCEED 24HRS ON BYPASS PLUG.

Note: Check air temperature, use a digital thermostat which can be purchased at any hardware

store under kitchen supplies.

Please refer to the images at the end of the document as a guide to where to measure the tempera- ture of the inlet/outlet air:

FIRST TEMPERATURE TEST:

1.Stabilize the unit by turning it on and letting it run for five minutes before performing the first temperature test.

2.Measure temperature of the inlet air going into the cooling unit on the evaporator (front) side.

3.Measure temperature of the outlet air discharging out of the cooling unit on the evaporator (front) side by holding the thermometer at the outer edge of the circular fan.

4.Record information and calculate temperature differential in table below for the evaporator (front) side section under the first test.

5.On the back side of the unit, measure temperature of the inlet air going into the cooling unit on the condenser (back) side.

6.On the back side of the unit, measure temperature of the outlet air discharging out of the cooling unit on the condenser (back) side by holding the thermometer at the outer edge of the circular fan.

7.Record information and calculate temperature differential in table below for the condenser/back side section under the first test.

SECOND TEMPERATURE TEST:

8.After the unit has run for 8 hours, perform the second temperature test.

9.Record information and calculate temperature differential in table below for the condenser/back side section under the second test.

Page 26

XLT 020111

Image 28
Contents XLT Page Table of Contents Owners Please NoteIntroduction What is the WhisperKOOL System?How does the WhisperKOOL System Work? Customer Warranty Registration ContentsReceiving & Inspecting the Unit Receiving and Inspecting the UnitQuick Start Guide Preparing the Wine Cellar Wall & Ceiling FramingMounting the Unit Unobstructed AirflowDoor Ambient Temperature Factor VentilationMark the horizontal lines with a level Tools NeededCut horizontal lines from stud to stud Cut vertical lines along the inside edge of the studs Frame the hole with two-by-four supportsInstallation Electrical NeedsElectrical Outlet Sizing Unit to RoomTesting Unit Applying Insulation TapeLiquid Measuring Thermostat System Attach precut foam tape to the unit’s flangeInstalling Thermostat Placement of UnitUsing the Whisperkool System Power SwitchCondensate Evaporator Switch Location of control switchesLiquid Measuring Thermostat System To Use the thermostatButtons PDT JR Operating InstructionsOperation PDT Operating Instructions PDTMaintenance Schedule MaintenanceNormal Operation Humidity ControlDucting Using the Thermostat Controller85F Max Airflow Troubleshooting GuideTry this first Air flows on both sides of the wall Door SealCool air drops and exits beneath door Thermostat Unit MountingMount WhisperKOOL high in the room Power Requirements CondensationIcing Up DrainlineRepairing Units Removing Rivets Consumer Care ProgramTroubleshooting Checklist General InspectionSpecific Performance Issues Unit is Not Cooling Sufficiently or Not Cooling at AllTemperature Differential Testing Do not Exceed 24HRS on Bypass PlugTemperature / Test time Evaporator Front Side Condenser Back SideInlet AIR -- Evaporator Front Side Inlet AIR -- Condenser Back SideConclusions Accessories for Cooling Units Technical AssistanceInstallation Terms and Conditions Five 5 Year Compressor Limited WarrantyProduct Warranty Limitations and Exclusions Product Installation RequirementsMaintenance Requirements WhisperKOOL Questions or Additional InformationModelXLTSerial NumberA WhisperKOOL