Southbend SSB-32, SSB-45, SSB-36 Specifications, Minimum Clearances From Combustible Construction

Page 4
SPECIFICATIONS

SPECIFICATIONS

RADIANT STEAKHOUSE BROILER

SPECIFICATIONS

NOTICE

Local codes regarding installation vary greatly from one area to another. The National Fire Protection Association, Inc. states in its NFPA 96 latest edition that local codes are the “authority having jurisdiction” when it comes to installation requirements for equipment. Therefore, installations must comply with all local codes, or in the absence of local codes, with the National Fuel Gas Code, ANSI Z223.1, Natural Gas Installation Code, CAN/CGA-B149.1, or the Propane Installation Code CAN/CGA-B149.2, as applicable, including:

1.The appliance and its individual shutoff valve must be disconnected from the gas supply piping system during any pressure testing of that system at test pressures in excess of 1/2 psi (3.45 kPa).

2.The appliance must be isolated from the gas supply piping system by closing its individual manual shutoff valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 1/2 psi (3.45 kPa).

Southbend reserves the right to change specifications and product design without notice. Such revisions do not entitle the buyer to corresponding changes, additions, or replacements for previously purchased equipment.

This product is intended for commercial use only, not for household use.

CLEARANCES

There must be adequate clearance between the broiler and adjacent construction due to the heat generated by the broiler. Clearance must also be provided for servicing and for operation.

The minimum clearance from non-combustible construction is 6 inches (152 mm) on the sides and rear (to permit combustion air to enter the rear of the broiler). To service the broiler components, all models require at least 6 inches (152 mm) accessibility-clearance on the right and left side.

Adequate clearance must be provided in front of the broiler for operation and cleaning.

The high-temperature flue products from the broiler burners flow out through a flue chamber at the top rear of the broiler. Installation under a vented hood is recommended.

CLEARANCES WARNING

MINIMUM CLEARANCES FROM COMBUSTIBLE CONSTRUCTION

The stand mount, cabinet mount and countertop model require a minimum clearance from combustible surfaces of 6 inches (152 mm) on the sides and rear.

PAGE 4 OF 20

OWNERS MANUAL 1190950 (02/09)

Image 4
Contents Models SSB-32, SSB-36, and SSB-45 Platinum Series Radiant Steakhouse BroilerFIRE HAZARD FOR YOUR SAFETY DANGERBURN HAZARD EXPLOSION AND ASPHYXIATION HAZARDINTRODUCTION Location of Serial PlateMINIMUM CLEARANCES FROM COMBUSTIBLE CONSTRUCTION SPECIFICATIONSCLEARANCES DIMENSIONS VENTILATIONTotal BTU’s BurnersGAS SUPPLY Gas TypeBurner Orifice Bar PilotDANGER EXPLOSION HAZARD OPERATIONOPERATION OF RADIANT STEAKHOUSE BROILER Broiler Controls and Components LIGHTING AFTER GAS HAS BEEN SHUT OFFLIGHTING BROILER PILOTS SHUTDOWN OF BROILERCLEANING & MAINTENANCE DAILY CLEANING AND MAINTENANCEMONTHLY CLEANING AND MAINTENANCE SEMIANNUAL CLEANING AND MAINTENANCESTAINLESS-STEEL SURFACES CARE OF GRIDDLESPAGE 10 OF IMMEDIATELY INSPECT FOR SHIPPING DAMAGE INSTALLATIONSTEP 1 UNPACKING Mounting Broiler on Stand STEP 2A MOUNT ON HEAVY DUTY STANDInstallation on Countertop STEP 2B ATTACH COUNTERTOP LEGSSTEP 3 CONNECT GAS SUPPLY STEP 4 CHECK THE INSTALLATIONPAGE 14 OF STEP 6 WIPE-CLEAN AND SHUT-DOWN APPLIANCE STEP 5 CHECK BROILER OPERATIONSERVICE TROUBLESHOOTINGProblem Look forACCESS TO SERVICEABLE PARTS Access to Serviceable PartsADJUSTMENT OF BROILER PILOTS ADJUSTMENT OF GAS PRESSURE REGULATOR ADJUSTMENT OF BROILER BURNERSPARTS PAGE 19 OF PLATINUM SERIES RADIANT STEAKHOUSE BROILER Stand Mount, Countertop, Cabinet Base or Refrigeration Base