DCA-400SSK — OUTPUTTERMINAL PANEL OVERVIEW
Output Terminal Panel Available Voltages
A wide range of voltages are available to supply load to many different applications. Voltages may be selected by using the voltage
TABLE 8. VOLTAGES AVAILABLE
MODEL | DCA400SSK |
|
|
|
|
| |
|
|
|
|
|
|
| |
3 PHASE VOLTAGE | 208 VOLT | 220 VOLT | 240 VOLT | 416 VOLT | 440 VOLT | 480 VOLT | |
(RECONNECTABLE) | |||||||
|
|
|
|
|
| ||
|
|
|
|
|
|
| |
SINGLE PHASE | 120 VOLT | 127 VOLT | 139 VOLT | 240 VOLT | 254 VOLT | 277 VOLT | |
(ADJUSTABLE) | |||||||
|
|
|
|
|
| ||
|
|
|
|
|
|
|
CAUTION :
NEVER attempt to change the Voltage
Over Current Relay
An over current relay is connected to the circuit breaker. In an over current situation, both the circuit breaker and the over current relay may trip. If the circuit breaker can not be reset, the reset button on the over current relay must be pressed. The over current relay is located in the control box.
Maximum Amps
The following table show the maximum amps the entire generator can provide. Do not exceed the maximum amps listed. (See Table 9)
Table 9. | Maximum Amps | |
|
| |
Model: | DCA400SSK | |
|
| |
Rated Voltage | Maximum Amps | |
|
| |
Single Phase 120 | 888.9 amps (4 wire) | |
Volt | ||
| ||
|
| |
Single Phase 240 | 444.4 amps (4 wire) | |
Volt | ||
| ||
|
| |
Three Phase | 962.3 amps | |
240 Volt | ||
| ||
|
| |
Three Phase | 481.1 amps | |
480 Volt | ||
| ||
|
|
PAGE 36 —