Outdoor Installation

Install the generator in a location where it will not be exposed to rain or sunshine. Make sure the generator is on secure level ground so that it cannot slide or shift around. Also install the generator in a manner so that the exhaust will not be discharged in the direction of nearby homes.

The installation site must be relatively free from moisture and dust. All electrical equipment should be protected from excessive moisture. Failure to do will result in deterioration of the insulation and will result in short circuits and grounding.

Foreign materials such as dust, sand, lint and abrasive materials have a tendency to cause excessive wear to engine and alternator parts.

CAUTION :

Pay close attention to ventilation when operating the generator inside tunnels and caves. The engine exhaust contains noxious elements. Engine exhaust must be routed to a ventilated area.

Indoor Installation

Exhaust gases from diesel engines are extremely poisonous. Whenever an engine is installed indoors the exhaust fumes must be vented to the outside.The engine should be installed at least two feet from any outside wall. Using an exhaust pipe which is too long or too small can cause excessive back pressure which will cause the engine to heat excessively and possibly burn the valves.

Mounting

The generator must be mounted on a solid foundation (such as concrete) and set firmly on the foundation to isolate vibration of the generator when it is running. The generator must set at least 6 inches above the floor or grade level (in accordance to NFPA 110, Chapter 5-4.1). DO NOT remove the metal skids on the bottom of the generator. They are to resist damage to the bottom of the generator and to maintain alignment.

DCA-400SSK — INSTALLATION

CAUTION :

An electric shock may happen when vibrators are used. Pay close attention to handling when operating vibrators and always use rubber boots and gloves to insulate the body from electrical shock.

Generator Grounding

To guard against electrical shock and possible damage to the equipment, it is important to provide a good EARTH ground.

Article 250 (Grounding) of the National Electrical Code (NEC) provides guide lines for proper grounding and specifies that the cable ground shall be connected to the grounding system of the building as close to the point of cable entry as practical.

NEC articles 250-64(b) and 250-66 set the following grounding requirements:

1.Use one of the following wire types to connect the generator to earth ground.

a.Copper - 10 AWG (5.3 mm2) or larger.

b.Aluminum - 8 AWG (8.4 mm2) or larger.

2.When grounding the generator (Figure 27) connect the ground cable between the lock washer and the nut on the generator and tighten the nut fully. Connect the other end of the ground cable to earth ground.

3.NEC article 250-52(c) specifies that the earth ground rod should be buried a minimum of 8 ft. into the ground.

NOTE

When connecting the generator to any buildings electrical system ALWAYS consult with a licensed electrician.

PAGE 40 — DCA-400SSK — PARTS AND OPERATION MANUAL (STD)— REV. #3 (09/17/01)

Image 40
Contents MQ Power DCA-400SSK DCA-400SSK2 Whisperwatttm Generator Page Heres HOW to GET Help Table of Contents Earn Extra Discounts when You order by FAX Parts Ordering ProceduresHigh Temperatures Allow Rules for Safe OperationRules for Safe Operation RadiatorBattery Loading and Unloading CraneTransporting Maintenance SafetyEmergencies Towing Safety Precautions DCA-400SSK -TOWINGDCA-400SSK TRAILER-SAFETY Guidelines Explanation of ChartDCA-400SSK -TRAILER-SPECIFICATIONS WidthModel Coupler Tires Wheels Axle Hubs Suspension Electrical Brakes Electric Brake AdjustmentElectric Brakes DCA-400SSK -TRAILER Safety Guidelines Hydraulic/Air/Surge BrakesTire Wear/Inflation Tires/Wheels/Lug NutsSuspension Torque Ft.-Lbs Lug Nut Torque RequirementsDCA-400SSK -TRAILER-WIRING Diagram DCA-400SSK -TRAILER-BRAKETROUBLESHOOTING Symptom Possible Cause SolutionDCA-400SSK -TRAILER-BRAKETROUBLESHOOTING DCA-400SSK Operation and Safety Decals Machine Safety DecalsDCA-400SSK Operation and Safety Decals DCA-400SSK Specifications DCA-400SSK General Information Battery Charger EngineElectronic Governor System JacketWater Heater OptionalDCA-400SSK Major Components Major ComponentsPage Dry weight 4270kg 9413.64lb Wet weight 4800kg 10582.08 lb DimensionsDCA-400SSK Dimensions Front and Rear DCA-400SSK Control Panel Control PanelDCA-400SSK Control Panel Pilot Lamp Indicates that the generator is working properlyDCA-400SSK Engine Operating Panel Ignition Switch up to S/N3696509 DCA-400SSK Engine Operating PanelDCA-400SSK Outputterminal Panel Overview DCA-400SSK Outputterminal Panel Overview Over Current Relay Output Terminal Panel Available VoltagesMaximum Amps How to read the output terminal gauges DCA-400SSK Outputterminal Panel OverviewSingle Phase, 240 Volt Phase, 240 VoltSingle Phase, 139 Volt Voltage Change-over BoardPhase, 480 Volt Single Phase, 480 VoltSingle Phase, 277 Volt Outdoor Installation DCA-400SSK InstallationMounting DCA-400SSK Installation Typical Generator Grounding ApplicationGeneral Inspection Prior to Operation DCA-400SSK PRE-SETUPExtension Cable Fuel Lubrication OilCoolant Cleaning the Radiator Air CleanerOperation in Freezing Weather Fan Belt TensionWiring Battery Cable InstallationPiping and Hose Connection Single Phase Load Three Phase LoadBefore Starting Engine Before Starting Generator and Control PanelDCA-400SSK Generator START-UP Procedure KEY Switch Engine Ignition Switch Ammeter Load Manual Start-up Auto Start-upEngine Shutdown DCA-400SSK Generator Shutdown ProcedureEmergency Stop Page DCA-400SSK Maintenance Changing Oil Check Electric Heater If equippedReplacing fuel filter Greasing Cleaning breather elementGenerator Storage Inspection / Maintenance DCA-400SSK Generator Wiring Diagram Page DCA-400SSK Engine Wiring Diagram KEY Switch DCA-400SSK Engine Wiring Diagram Controller DCA-400SSK -TROUBLESHOOTING Engine DCA-400SSK -TROUBLESHOOTING Engine DCA-400SSK -TROUBLESHOOTING GENERATOR/ENGINE Generator TroubleshootingDCA-400SSK -TROUBLESHOOTING Engine Controller Explanation of Code in Remarks Column Items Found In the Items Number ColumnDCA-400SSK Suggested Spare Parts Qty DescriptionDCA-400SSK Generator Assy Part Name QTY DCA-400SSK Generator Assy COVER, Bearing DCA-400SSK Control BOX Assy DCA-400SSK Control BOX Assy Part Name QTY RemarksDCA-400SSK Control BOX Assy RA20A2SE102BJ 2W 1K OHM DCA-400SSK Engine & Radiator Assy Dust Sensor DCA-400SSK Engine & Radiator Assy DCA-400SSK Engine & Radiator Assy DCA-400SSKENGINE Operating Panel Assy UP to S/N 3701677~DCA-400SSK Engine Operating Panel Assy DCA-400SSK Outputterminal Assy DCA-400SSK Output Terminal Assy DCA-400SSK Battery Assy Battery DCA-400SSK Actuator Assy DYNC11020300024 DCA-400SSK Muffler Assy Muffler DCA-400SSK Fuel Tank Assy Fuel Tank DCA-400SSK Enclosure #1 Assy Floor Panel DCA-400SSK Enclosure #1 Assy Filler Bracket DCA-400SSK Enclosure #2 Assy Enclosure #2 AssyRear Frame DCA-400SSK Enclosure #2 Assy COVER, Roof Panel DCA-400SSK Enclosure #3 Assy Enclosure #3 AssySide Panel DCA-400SSK Enclosure #3 Assy 0845046904 DCA-400SSK Rubber Seal Assy Rubber Seal Assy DCA-400SSK OIL Piping Assy Pump DCA-400SSK Name Plate and Decals N3701677~Control BOX Group Bonnet Group Battery Group Engine and Radiator Group DCA-400SSK Name Plate and Decals Output Terminal GroupEffective July 1 Page Mail mq@multiquip.com WWW multiquip.com

DCA-400SSK specifications

The Multiquip DCA-400SSK is a robust solution designed for a variety of construction and developmental applications. Known for its reliability and efficiency, this three-phase diesel generator is equipped with a powerful engine that offers dependable performance in the field.

One of the standout features of the DCA-400SSK is its 400 kW output capacity, making it an ideal choice for large-scale operations where consistent power supply is crucial. It is powered by a high-performance, durable diesel engine that meets stringent emissions standards, ensuring compliance while delivering high efficiency.

The DCA-400SSK comes equipped with advanced technology that enhances its usability and performance. Its automatic voltage regulation (AVR) system ensures stable voltage under varying load conditions, which is essential for sensitive electrical equipment. This feature provides peace of mind to operators, knowing that their equipment is protected from voltage fluctuations.

Built with a sound-attenuated enclosure, the DCA-400SSK is designed to minimize noise, making it suitable for operation in noise-sensitive environments. This aspect not only protects the hearing of those working nearby but also ensures compliance with local noise regulations, thereby promoting a safer working environment.

Another remarkable characteristic of the DCA-400SSK is its user-friendly control panel, which features easy-to-read gauges and straightforward controls. This makes monitoring and operating the generator simple, even for those with limited experience in generator operation. With remote start capabilities, users can start and stop the generator from a distance, enhancing efficiency and convenience.

In terms of mobility, the DCA-400SSK is designed with integrated lifting points and forklift pockets, which facilitate easy transport around job sites. Its rugged construction ensures durability, able to withstand the harsh conditions typical of construction sites while maintaining optimal performance.

Overall, the Multiquip DCA-400SSK stands as a reliable and efficient diesel generator, combining powerful output with advanced features and environmental considerations. It is tailored to meet the demands of contractors and operators looking for a versatile and sturdy power solution. Whether for temporary power needs or long-term projects, the DCA-400SSK delivers exceptional performance in a compact and user-friendly package.