Single Phase Load
Always be sure to check the nameplate on the generator and equipment to insure the wattage, amperage and frequency requirements are satisfactorily supplied by the generator for operating the equipment.
Generally, the wattage listed on the nameplate of the equipment is its rated output. Equipment may require 130— 150% more wattage than the rating on the nameplate, as the wattage is influenced by the efficiency, power factor and starting system of the equipment.
NOTE
If wattage is not given on the equipment's name plate, approximate wattage may be determined by multiplying nameplate voltage by the nameplate amperage.
WATTS = VOLTAGE x AMPERAGE
The power factor of this generator is 0.8. See Table 14. below when connecting loads.
DCA-400SSK — LOAD APPLICATION
CAUTION:
Motors and
An inadequate size connecting cable which cannot carry the required load can cause a voltage drop which can burn out the appliance or tool and overheat the cable.
zWhen connecting a resistance load such as an incandescent lamp or electric heater, a capacity of up to the generating set’s rated output (kW) can be used.
zWhen connecting a fluorescent or mercury lamp, a capacity of up to the generating set’s rated output (kW) multiplied by 0.6 can be used.
zWhen connecting an electric drill or other power tools, pay close attention to the required starting current capacity.
When connecting ordinary power tools, a capacity of up to the generating set’s rated output (kW) multiplied by 0.8 can be used.
Table 14. Power Factor By Load
Type Of Load | Power Factor | |
|
| |
0.4 - 0.75 | ||
|
| |
Electric heaters, incandescent | 1.0 | |
lamps | ||
| ||
|
| |
Fluorescent lamps, mercury lamps | 0.4 - 0.9 | |
|
| |
Electronic devices, communication | 1.0 | |
equipment | ||
| ||
|
|
Three Phase Load
When calculating the power requirements for
CAUTION:
Before connecting this generator to any building’s electrical system, a licensed electrician must install an isolation (transfer) switch. Serious injury or death may result without this transfer switch.
NOTE
If output (kVA) is not given on the equipment nameplate, approximate output may be determined by multiplying voltage by
amperage by and 1.732.