Installation
Electrical Specifications
40 Pound Capacity Models
| 
 | Voltage Designation | 
 | 
 | 
 | Standard | 
 | 
 | Electric Heat | 
 | |||||
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
| Code | Voltage | Cycle | 
 | Phase | Wire | FullLoad Amps | Circuit Breaker | AWG | 2 | FullLoad Amps | Circuit Breaker | 
 | AWG | 2 | 
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | mm | 
 | 
 | 
 | 
 | mm | 
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
| 
 | 
 | 
 | 
 | 
 | 
 | 2 Speed Models | 
 | 
 | 
 | 
 | 
 | 
 | ||
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
| C | 380 – 415 | 50 | 
 | 3 | 4 | 5 | 15 | 14 | 2.5 | 27 | 30 | 
 | 10 | 6.0 | 
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
| F | 440 – 480 | 60 | 
 | 3 | 3 | 5 | 15 | 14 | 2.5 | 24 | 30 | 
 | 10 | 6.0 | 
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
| J | 200 | 50 | 
 | 3 | 3 | 7 | 20 | 12 | 4.0 | 
 | N/A | 
 | 
 | |
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
| O | 208 – 240 | 60 | 
 | 3 | 3 | 7 | 20 | 12 | 4.0 | 45 | 50 | 
 | 8 | 10.0 | 
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
| Y | 208 – 240 | 60 | 
 | 1 | 2 | 14 | 30 | 10 | 6.0 | 
 | N/A | 
 | 
 | |
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | ||
| R | 380 – 480 | 50/60 | 
 | 3 | 3 | 6 | 15 | 14 | 2.5 | 23 | 30 | 
 | 10 | 6.0 | 
| (through | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
| 7/6/10) | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
| N | 440 – 480 | 60 | 
 | 3 | 3 | 5 | 15 | 14 | 2.5 | 22 | 30 | 
 | 10 | 6.0 | 
| (starting | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
| 7/7/10) | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
| P | 380 – 415 | 50 | 
 | 3 | 3 | 5 | 15 | 14 | 2.5 | 22 | 30 | 
 | 10 | 6.0 | 
| (starting | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
| 7/7/10) | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
| Q | 200 – 240 | 50/60 | 
 | 3 | 3 | 6 | 15 | 14 | 2.5 | 42 | 50 | 
 | 8 | 10.0 | 
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
| X | 200 – 240 | 50/60 | 
 | 1/3 | 2/3 | 10/6 | 15 | 14 | 2.5 | 
 | N/A | 
 | 
 | |
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
NOTE: Wire sizes shown are for copper, THHN, 90°C conductor per NEC article 310.
Table 12
| F8208301 | © Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT | 49 |