■ Ensure that each wiring closet has a suitable ground. All metal racks,

Distribution Rack Requirements 107

Ensure that all wiring closets have doors with locks to prevent unauthorized access.

Provide adequate overhead lighting in the wiring closet for easy maintenance.

Ensure that each wiring closet has a suitable ground. All metal racks,

 

enclosures, boxes, and raceways in the closet should be grounded.

 

Assign wiring closet identification numbers using architectural

 

location codes or some type of floor grid matrix.

 

Ensure that all system environmental requirements are met (such as

 

ambient temperature and humidity).

 

 

 

 

 

Distribution Rack

This section describes the basic mechanical and space requirements for

Requirements

the distribution rack (refer to Figure 16).

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Figure 16 Distribution racks

Mechanical Racks should comply with the standards and requirements mentioned in Requirements the cabling system plan and should conform to conventional standards.

In the United States, use EIA Standard RS-310C: Racks, Panels, and Associated Equipment. In countries other than the United States, use IEC Standard 297: Dimensions of Panels and Racks.

The following are distribution rack requirements: