TABLE 5, COMBINED VENT SIZING TABLES
MODEL HW-300 BOILER
| Input: 300,000 Btuh |
|
|
|
|
|
| Draft Hood Outlet 8" |
|
|
| ||||
| Required Connector or | Smoke Pipe Diameter |
|
|
|
|
| ||||||||
| Connector |
| Total Vent Height (Measured in Feet Above Draft Hood) |
| |||||||||||
| 10 |
| 15 | 20 | 30 |
| 40 | 50 | 60 |
| 80 |
| 100 | ||
| Rise in Feet |
|
|
|
| ||||||||||
|
|
|
|
| Connector Diameter (in Inches) |
|
|
| |||||||
|
|
|
|
|
|
|
|
| |||||||
| 1 | 10 |
| 10 | 10 | 10 |
| 10 | 10 | 10 |
| 10 |
| 10 | |
| 2 | 10 |
| 10 | 10 | 10 |
| 10 | 10 | 10 |
| 10 |
| 10 | |
| 3 | 10 |
| 10 | 10 | 10 |
| 10 | 10 | 10 |
| 10 |
| 10 | |
| 4 or more |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Number | Total Input |
| Total Vent Height (Measured in Feet Above Draft Hood) |
| |||||||||||
if Units | 10 |
| 15 | 20 | 30 |
| 40 | 50 | 60 |
| 80 |
| 100 | ||
Btuh x 1000 |
|
|
|
| |||||||||||
Combined |
|
| Manifold and Common Vent Diameter (in Inches) |
| |||||||||||
|
|
|
| ||||||||||||
2 | 600 | 14 |
| 12 | 12 | 12 |
| 10 | 10 | 10 |
| 10 |
| 10 | |
3 | 900 | 16 |
| 14 | 14 | 14 |
| 12 | 12 | 12 |
| 12 |
| 12 | |
4 | 1200 | 18 |
| 16 | 16 | 14 |
| 14 | 14 | 14 |
| 12 |
| 12 | |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
| MODEL |
|
|
|
|
|
|
| ||||||
| Input: 399,000 Btuh |
|
|
|
|
|
| Draft Hood Outlet 10" |
|
|
| ||||
| Required Connector or | Smoke Pipe Diameter |
|
|
|
|
| ||||||||
| Connector |
| Total Vent Height (Measured in Feet Above Draft Hood) |
| |||||||||||
| 10 |
| 15 | 20 | 30 |
| 40 | 50 | 60 |
| 80 |
| 100 | ||
| Rise in Feet |
|
|
|
| ||||||||||
|
|
|
|
| Connector Diameter (in Inches) |
|
|
| |||||||
|
|
|
|
|
|
|
|
| |||||||
| 1 | 12 |
| 12 | 12 | 12 |
| 12 | 12 | 12 |
| 12 |
| 12 | |
| 2 | 12 |
| 12 | 12 | 10 |
| 10 | 10 | 10 |
| 10 |
| 10 | |
| 3 | 12 |
| 10 | 10 | 10 |
| 10 | 10 | 10 |
| 10 |
| 10 | |
| 4 or more | 10 |
| 10 | 10 | 10 |
| 10 | 10 | 10 |
| 10 |
| 10 | |
Number | Total Input |
| Total Vent Height (Measured in Feet Above Draft Hood) |
| |||||||||||
if Units | 10 |
| 15 | 20 | 30 |
| 40 | 50 | 60 |
| 80 |
| 100 | ||
Btuh x 1000 |
|
|
|
| |||||||||||
Combined |
|
| Manifold and Common Vent Diameter (in Inches) |
| |||||||||||
|
|
|
| ||||||||||||
2 | 798 | 14 |
| 14 | 14 | 12 |
| 12 | 12 | 12 |
| 12 |
| 12 | |
3 | 1197 | 18 |
| 16 | 16 | 14 |
| 14 | 14 | 14 |
| 14 |
| 12 | |
4 | 1596 | 20 |
| 20 | 18 | 16 |
| 16 | 16 | 14 |
| 14 |
| 14 | |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
| MODEL |
|
|
|
|
|
|
| ||||||
| Input: 420,000 Btuh |
|
|
|
|
|
| Draft Hood Outlet 10" |
|
|
| ||||
| Required Connector or | Smoke Pipe Diameter |
|
|
|
|
| ||||||||
| Connector |
| Total Vent Height (Measured in Feet Above Draft Hood) |
| |||||||||||
| 10 |
| 15 | 20 | 30 |
| 40 | 50 | 60 |
| 80 |
| 100 | ||
| Rise in Feet |
|
|
|
| ||||||||||
|
|
|
|
| Connector Diameter (in Inches) |
|
|
| |||||||
|
|
|
|
|
|
|
|
| |||||||
| 1 | 12 |
| 12 | 12 | 12 |
| 12 | 12 | 12 |
| 12 |
| 12 | |
| 2 | 12 |
| 12 | 12 | 10 |
| 10 | 10 | 10 |
| 10 |
| 10 | |
| 3 | 12 |
| 10 | 10 | 10 |
| 10 | 10 | 10 |
| 10 |
| 10 | |
| 4 or more | 10 |
| 10 | 10 | 10 |
| 10 | 10 | 10 |
| 10 |
| 10 | |
Number | Total Input |
| Total Vent Height (Measured in Feet Above Draft Hood) |
| |||||||||||
if Units | 10 |
| 15 | 20 | 30 |
| 40 | 50 | 60 |
| 80 |
| 100 | ||
Btuh x 1000 |
|
|
|
| |||||||||||
Combined |
|
| Manifold and Common Vent Diameter (in Inches) |
| |||||||||||
|
|
|
| ||||||||||||
2 | 840 | 14 |
| 14 | 14 | 12 |
| 12 | 12 | 12 |
| 12 |
| 12 | |
3 | 1260 | 18 |
| 16 | 16 | 14 |
| 14 | 14 | 14 |
| 14 |
| 12 | |
4 | 1680 | 20 |
| 20 | 18 | 16 |
| 16 | 16 | 14 |
| 14 |
| 14 | |
|
|
|
|
|
|
|
|
|
|
| |||||
|
| MODEL |
|
|
|
|
|
|
| ||||||
| Input: 520,000 Btuh |
|
|
|
|
|
| Draft Hood Outlet 10" |
|
|
| ||||
| Required Connector or | Smoke Pipe Diameter |
|
|
|
|
| ||||||||
| Connector |
| Total Vent Height (Measured in Feet Above Draft Hood) |
| |||||||||||
| 10 |
| 15 | 20 | 30 |
| 40 | 50 | 60 |
| 80 |
| 100 | ||
| Rise in Feet |
|
|
|
| ||||||||||
|
|
|
|
| Connector Diameter (in Inches) |
|
|
| |||||||
|
|
|
|
|
|
|
|
| |||||||
| 1 | 14 |
| 14 | 14 | 12 |
| 12 | 12 | 12 |
| 12 |
| 12 | |
| 2 | 12 |
| 12 | 12 | 12 |
| 12 | 12 | 12 |
| 12 |
| 12 | |
| 3 | 12 |
| 12 | 12 | 12 |
| 10 | 10 | 10 |
| 10 |
| 10 | |
| 4 or more | 12 |
| 12 | 12 | 12 |
| 10 | 10 | 10 |
| 10 |
| 10 | |
Number | Total Input |
| Total Vent Height (Measured in Feet Above Draft Hood) |
| |||||||||||
if Units | 10 |
| 15 | 20 | 30 |
| 40 | 50 | 60 |
| 80 |
| 100 | ||
Btuh x 1000 |
|
|
|
| |||||||||||
Combined |
|
| Manifold and Common Vent Diameter (in Inches) |
| |||||||||||
|
|
|
| ||||||||||||
2 | 1040 | 16 |
| 16 | 14 | 14 |
| 14 | 14 | 12 |
| 12 |
| 12 | |
3 | 1560 | 20 |
| 18 | 18 | 16 |
| 16 | 14 | 14 |
| 14 |
| 14 | |
4 | 2080 | 22 |
| 22 | 20 | 18 |
| 18 | 18 | 16 |
| 16 |
| 14 | |
5 | 2600 | 26 |
| 24 | 22 | 20 |
| 20 | 18 | 18 |
| 18 |
| 18 | |
6 | 3120 | 28 |
| 26 | 24 | 22 |
| 22 | 20 | 20 |
| 18 |
| 18 | |
7 | 3640 | 30 |
| 28 | 26 | 24 |
| 24 | 22 | 22 |
| 20 |
| 20 | |
8 | 4160 | 32 |
| 30 | 28 | 26 |
| 24 | 24 | 22 |
| 22 |
| 20 |
MODEL HW-610 BOILER
| Input: 610,000 Btuh |
|
|
|
|
|
| Draft Hood Outlet 12" |
|
|
| ||||
| Required Connector or | Smoke Pipe Diameter |
|
|
|
|
| ||||||||
| Connector |
| Total Vent Height (Measured in Feet Above Draft Hood) |
| |||||||||||
| 10 |
| 15 | 20 | 30 |
| 40 | 50 | 60 |
| 80 |
| 100 | ||
| Rise in Feet |
|
|
|
| ||||||||||
|
|
|
|
| Connector Diameter (in Inches) |
|
|
| |||||||
|
|
|
|
|
|
|
|
| |||||||
| 1 | 16 |
| 14 | 14 | 14 |
| 14 | 14 | 14 |
| 14 |
| 14 | |
| 2 | 14 |
| 14 | 14 | 14 |
| 14 | 12 | 12 |
| 12 |
| 12 | |
| 3 | 14 |
| 14 | 12 | 12 |
| 12 | 12 | 12 |
| 12 |
| 12 | |
| 4 or more | 12 |
| 12 | 12 | 12 |
| 12 | 12 | 12 |
| 12 |
| 12 | |
Number | Total Input |
| Total Vent Height (Measured in Feet Above Draft Hood) |
| |||||||||||
if Units | 10 |
| 15 | 20 | 30 |
| 40 | 50 | 60 |
| 80 |
| 100 | ||
Btuh x 1000 |
|
|
|
| |||||||||||
Combined |
|
| Manifold and Common Vent Diameter (in Inches) |
| |||||||||||
|
|
|
| ||||||||||||
2 | 1220 | 18 |
| 18 | 16 | 16 |
| 14 | 14 | 14 |
| 14 |
| 14 | |
3 | 1830 | 22 |
| 20 | 20 | 18 |
| 18 | 16 | 16 |
| 16 |
| 14 | |
4 | 2440 | 26 |
| 24 | 22 | 20 |
| 20 | 18 | 18 |
| 18 |
| 16 | |
5 | 3050 | 28 |
| 26 | 26 | 24 |
| 22 | 22 | 20 |
| 20 |
| 18 | |
6 | 3660 | 32 |
| 28 | 28 | 26 |
| 24 | 24 | 22 |
| 22 |
| 20 | |
7 | 4270 | 34 |
| 32 | 30 | 28 |
| 26 | 24 | 24 |
| 22 |
| 22 | |
8 | 4880 | 36 |
| 34 | 32 | 30 |
| 28 | 26 | 26 |
| 24 |
| 24 | |
9 | 5490 | 38 |
| 36 | 34 | 30 |
| 30 | 28 | 28 |
| 26 |
| 24 | |
10 | 6100 | 40 |
| 38 | 36 | 32 |
| 30 | 30 | 28 |
| 26 |
| 26 | |
11 | 6710 | 42 |
| 38 | 38 | 34 |
| 32 | 30 | 28 |
| 28 |
| 26 | |
12 | 7320 | 44 |
| 42 | 38 | 36 |
| 34 | 32 | 32 |
| 30 |
| 28 | |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
| MODEL |
|
|
|
|
|
|
| ||||||
Input: 660,000 or 670,000 Btuh |
|
|
|
| Draft Hood Outlet 12" |
|
|
| |||||||
| Required Connector or | Smoke Pipe Diameter |
|
|
|
|
| ||||||||
| Connector |
| Total Vent Height (Measured in Feet Above Draft Hood) |
| |||||||||||
| 10 |
| 15 | 20 | 30 |
| 40 | 50 | 60 |
| 80 |
| 100 | ||
| Rise in Feet |
|
|
|
| ||||||||||
|
|
|
|
| Connector Diameter (in Inches) |
|
|
| |||||||
|
|
|
|
|
|
|
|
| |||||||
| 1 | 16 |
| 14 | 14 | 14 |
| 14 | 14 | 14 |
| 14 |
| 14 | |
| 2 | 14 |
| 14 | 14 | 14 |
| 14 | 12 | 12 |
| 12 |
| 12 | |
| 3 | 14 |
| 14 | 12 | 12 |
| 12 | 12 | 12 |
| 12 |
| 12 | |
| 4 or more | 12 |
| 12 | 12 | 12 |
| 12 | 12 | 12 |
| 12 |
| 12 | |
Number | Total Input |
| Total Vent Height (Measured in Feet Above Draft Hood) |
| |||||||||||
if Units | 10 |
| 15 | 20 | 30 |
| 40 | 50 | 60 |
| 80 |
| 100 | ||
Btuh x 1000 |
|
|
|
| |||||||||||
Combined |
|
| Manifold and Common Vent Diameter (in Inches) |
| |||||||||||
|
|
|
| ||||||||||||
2 | 1220 | 18 |
| 18 | 16 | 16 |
| 14 | 14 | 14 |
| 14 |
| 14 | |
3 | 1830 | 22 |
| 20 | 20 | 18 |
| 18 | 16 | 16 |
| 16 |
| 14 | |
4 | 2440 | 26 |
| 24 | 22 | 20 |
| 20 | 18 | 18 |
| 18 |
| 16 | |
5 | 3050 | 28 |
| 26 | 26 | 24 |
| 22 | 22 | 20 |
| 20 |
| 18 | |
6 | 3660 | 32 |
| 28 | 28 | 26 |
| 24 | 24 | 22 |
| 22 |
| 20 | |
7 | 4270 | 34 |
| 32 | 30 | 28 |
| 26 | 24 | 24 |
| 22 |
| 22 | |
8 | 4880 | 36 |
| 34 | 32 | 30 |
| 28 | 26 | 26 |
| 24 |
| 24 | |
9 | 5490 | 38 |
| 36 | 34 | 30 |
| 30 | 28 | 28 |
| 26 |
| 24 | |
10 | 6100 | 40 |
| 38 | 36 | 32 |
| 30 | 30 | 28 |
| 26 |
| 26 | |
11 | 6710 | 42 |
| 38 | 38 | 34 |
| 32 | 30 | 28 |
| 28 |
| 26 | |
12 | 7320 | 46 |
| 44 | 40 | 38 |
| 36 | 34 | 34 |
| 32 |
| 30 |
Known: (5) model
Problem: Determine diameter of connector, manifold and common vent.
Procedure: Enter the top of the
To determine the manifold and common vent size, enter table on this page (total vent height) at 30 and the side at 5 boilers. A manifold diameter of 24" (610 mm) is indicated.
17