TABLE 5, COMBINED VENT SIZING TABLES

MODEL HW-300 BOILER

 

Input: 300,000 Btuh

 

 

 

 

 

 

Draft Hood Outlet 8"

 

 

 

 

Required Connector or

Smoke Pipe Diameter

 

 

 

 

 

 

Connector

 

Total Vent Height (Measured in Feet Above Draft Hood)

 

 

10

 

15

20

30

 

40

50

60

 

80

 

100

 

Rise in Feet

 

 

 

 

 

 

 

 

 

Connector Diameter (in Inches)

 

 

 

 

 

 

 

 

 

 

 

 

 

1

10

 

10

10

10

 

10

10

10

 

10

 

10

 

2

10

 

10

10

10

 

10

10

10

 

10

 

10

 

3

10

 

10

10

10

 

10

10

10

 

10

 

10

 

4 or more

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Number

Total Input

 

Total Vent Height (Measured in Feet Above Draft Hood)

 

if Units

10

 

15

20

30

 

40

50

60

 

80

 

100

Btuh x 1000

 

 

 

 

Combined

 

 

Manifold and Common Vent Diameter (in Inches)

 

 

 

 

 

2

600

14

 

12

12

12

 

10

10

10

 

10

 

10

3

900

16

 

14

14

14

 

12

12

12

 

12

 

12

4

1200

18

 

16

16

14

 

14

14

14

 

12

 

12

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MODEL HW-399 BOILER

 

 

 

 

 

 

 

 

Input: 399,000 Btuh

 

 

 

 

 

 

Draft Hood Outlet 10"

 

 

 

 

Required Connector or

Smoke Pipe Diameter

 

 

 

 

 

 

Connector

 

Total Vent Height (Measured in Feet Above Draft Hood)

 

 

10

 

15

20

30

 

40

50

60

 

80

 

100

 

Rise in Feet

 

 

 

 

 

 

 

 

 

Connector Diameter (in Inches)

 

 

 

 

 

 

 

 

 

 

 

 

 

1

12

 

12

12

12

 

12

12

12

 

12

 

12

 

2

12

 

12

12

10

 

10

10

10

 

10

 

10

 

3

12

 

10

10

10

 

10

10

10

 

10

 

10

 

4 or more

10

 

10

10

10

 

10

10

10

 

10

 

10

Number

Total Input

 

Total Vent Height (Measured in Feet Above Draft Hood)

 

if Units

10

 

15

20

30

 

40

50

60

 

80

 

100

Btuh x 1000

 

 

 

 

Combined

 

 

Manifold and Common Vent Diameter (in Inches)

 

 

 

 

 

2

798

14

 

14

14

12

 

12

12

12

 

12

 

12

3

1197

18

 

16

16

14

 

14

14

14

 

14

 

12

4

1596

20

 

20

18

16

 

16

16

14

 

14

 

14

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MODEL HW-420 BOILER

 

 

 

 

 

 

 

 

Input: 420,000 Btuh

 

 

 

 

 

 

Draft Hood Outlet 10"

 

 

 

 

Required Connector or

Smoke Pipe Diameter

 

 

 

 

 

 

Connector

 

Total Vent Height (Measured in Feet Above Draft Hood)

 

 

10

 

15

20

30

 

40

50

60

 

80

 

100

 

Rise in Feet

 

 

 

 

 

 

 

 

 

Connector Diameter (in Inches)

 

 

 

 

 

 

 

 

 

 

 

 

 

1

12

 

12

12

12

 

12

12

12

 

12

 

12

 

2

12

 

12

12

10

 

10

10

10

 

10

 

10

 

3

12

 

10

10

10

 

10

10

10

 

10

 

10

 

4 or more

10

 

10

10

10

 

10

10

10

 

10

 

10

Number

Total Input

 

Total Vent Height (Measured in Feet Above Draft Hood)

 

if Units

10

 

15

20

30

 

40

50

60

 

80

 

100

Btuh x 1000

 

 

 

 

Combined

 

 

Manifold and Common Vent Diameter (in Inches)

 

 

 

 

 

2

840

14

 

14

14

12

 

12

12

12

 

12

 

12

3

1260

18

 

16

16

14

 

14

14

14

 

14

 

12

4

1680

20

 

20

18

16

 

16

16

14

 

14

 

14

 

 

 

 

 

 

 

 

 

 

 

 

 

MODEL HW-520 BOILER

 

 

 

 

 

 

 

 

Input: 520,000 Btuh

 

 

 

 

 

 

Draft Hood Outlet 10"

 

 

 

 

Required Connector or

Smoke Pipe Diameter

 

 

 

 

 

 

Connector

 

Total Vent Height (Measured in Feet Above Draft Hood)

 

 

10

 

15

20

30

 

40

50

60

 

80

 

100

 

Rise in Feet

 

 

 

 

 

 

 

 

 

Connector Diameter (in Inches)

 

 

 

 

 

 

 

 

 

 

 

 

 

1

14

 

14

14

12

 

12

12

12

 

12

 

12

 

2

12

 

12

12

12

 

12

12

12

 

12

 

12

 

3

12

 

12

12

12

 

10

10

10

 

10

 

10

 

4 or more

12

 

12

12

12

 

10

10

10

 

10

 

10

Number

Total Input

 

Total Vent Height (Measured in Feet Above Draft Hood)

 

if Units

10

 

15

20

30

 

40

50

60

 

80

 

100

Btuh x 1000

 

 

 

 

Combined

 

 

Manifold and Common Vent Diameter (in Inches)

 

 

 

 

 

2

1040

16

 

16

14

14

 

14

14

12

 

12

 

12

3

1560

20

 

18

18

16

 

16

14

14

 

14

 

14

4

2080

22

 

22

20

18

 

18

18

16

 

16

 

14

5

2600

26

 

24

22

20

 

20

18

18

 

18

 

18

6

3120

28

 

26

24

22

 

22

20

20

 

18

 

18

7

3640

30

 

28

26

24

 

24

22

22

 

20

 

20

8

4160

32

 

30

28

26

 

24

24

22

 

22

 

20

MODEL HW-610 BOILER

 

Input: 610,000 Btuh

 

 

 

 

 

 

Draft Hood Outlet 12"

 

 

 

 

Required Connector or

Smoke Pipe Diameter

 

 

 

 

 

 

Connector

 

Total Vent Height (Measured in Feet Above Draft Hood)

 

 

10

 

15

20

30

 

40

50

60

 

80

 

100

 

Rise in Feet

 

 

 

 

 

 

 

 

 

Connector Diameter (in Inches)

 

 

 

 

 

 

 

 

 

 

 

 

 

1

16

 

14

14

14

 

14

14

14

 

14

 

14

 

2

14

 

14

14

14

 

14

12

12

 

12

 

12

 

3

14

 

14

12

12

 

12

12

12

 

12

 

12

 

4 or more

12

 

12

12

12

 

12

12

12

 

12

 

12

Number

Total Input

 

Total Vent Height (Measured in Feet Above Draft Hood)

 

if Units

10

 

15

20

30

 

40

50

60

 

80

 

100

Btuh x 1000

 

 

 

 

Combined

 

 

Manifold and Common Vent Diameter (in Inches)

 

 

 

 

 

2

1220

18

 

18

16

16

 

14

14

14

 

14

 

14

3

1830

22

 

20

20

18

 

18

16

16

 

16

 

14

4

2440

26

 

24

22

20

 

20

18

18

 

18

 

16

5

3050

28

 

26

26

24

 

22

22

20

 

20

 

18

6

3660

32

 

28

28

26

 

24

24

22

 

22

 

20

7

4270

34

 

32

30

28

 

26

24

24

 

22

 

22

8

4880

36

 

34

32

30

 

28

26

26

 

24

 

24

9

5490

38

 

36

34

30

 

30

28

28

 

26

 

24

10

6100

40

 

38

36

32

 

30

30

28

 

26

 

26

11

6710

42

 

38

38

34

 

32

30

28

 

28

 

26

12

7320

44

 

42

38

36

 

34

32

32

 

30

 

28

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MODEL HW-670 BOILER

 

 

 

 

 

 

 

Input: 660,000 or 670,000 Btuh

 

 

 

 

Draft Hood Outlet 12"

 

 

 

 

Required Connector or

Smoke Pipe Diameter

 

 

 

 

 

 

Connector

 

Total Vent Height (Measured in Feet Above Draft Hood)

 

 

10

 

15

20

30

 

40

50

60

 

80

 

100

 

Rise in Feet

 

 

 

 

 

 

 

 

 

Connector Diameter (in Inches)

 

 

 

 

 

 

 

 

 

 

 

 

 

1

16

 

14

14

14

 

14

14

14

 

14

 

14

 

2

14

 

14

14

14

 

14

12

12

 

12

 

12

 

3

14

 

14

12

12

 

12

12

12

 

12

 

12

 

4 or more

12

 

12

12

12

 

12

12

12

 

12

 

12

Number

Total Input

 

Total Vent Height (Measured in Feet Above Draft Hood)

 

if Units

10

 

15

20

30

 

40

50

60

 

80

 

100

Btuh x 1000

 

 

 

 

Combined

 

 

Manifold and Common Vent Diameter (in Inches)

 

 

 

 

 

2

1220

18

 

18

16

16

 

14

14

14

 

14

 

14

3

1830

22

 

20

20

18

 

18

16

16

 

16

 

14

4

2440

26

 

24

22

20

 

20

18

18

 

18

 

16

5

3050

28

 

26

26

24

 

22

22

20

 

20

 

18

6

3660

32

 

28

28

26

 

24

24

22

 

22

 

20

7

4270

34

 

32

30

28

 

26

24

24

 

22

 

22

8

4880

36

 

34

32

30

 

28

26

26

 

24

 

24

9

5490

38

 

36

34

30

 

30

28

28

 

26

 

24

10

6100

40

 

38

36

32

 

30

30

28

 

26

 

26

11

6710

42

 

38

38

34

 

32

30

28

 

28

 

26

12

7320

46

 

44

40

38

 

36

34

34

 

32

 

30

Known: (5) model HW-610 boilers. (See illustration). Connector rise - 2' (Note 1' is minimum). Total vent height 30'.

Problem: Determine diameter of connector, manifold and common vent.

Procedure: Enter the top of the HW-610 table (total vent height) at 30' and the side at 2' (connector rise). A 14" connector diameter is indicated for each connector rise.

To determine the manifold and common vent size, enter table on this page (total vent height) at 30 and the side at 5 boilers. A manifold diameter of 24" (610 mm) is indicated.

17

Page 17
Image 17
A.O. Smith HW 610 warranty Combined Vent Sizing Tables, Model HW-300 Boiler