Installation | 152-388-100-02, Issue 2 |
| |
VERIFICATION
Once the H2TU-C-388 List 1 is installed, verify that it is operating properly. To do this, monitor the following:
•Status LED
•Status messages reported by the front-panel display (see Table 2 on page 5)
Verification without a Downstream Device
If there is no downstream device installed:
1Verify that the H2TU-C powers up. The front-panel display illuminates and reports status messages. (See Table 2 on page 5 for a list of messages.)
2Verify that the H2TU-C attempts to communicate with downstream devices (status LED flashes red). Even if a downstream device is not present, the following events should occur:
a The front-panel display reports various four-character status messages.
b The H2TU-C again attempts communication with downstream devices until a downstream device is detected.
Verification with a Downstream Device
If a downstream device has been installed:
1Verify that the H2TU-C powers up. (The front-panel display illuminates and reports various status messages.)
2Verify that the H2TU-C attempts to communicate with downstream devices (status LED flashes red). One of the following occurs:
•If downstream devices are successfully identified and the HDSL2 loop synchronizes, the H2TU-C status LED lights steady green. The H2TU-C reports normal margin messages on the front-panel display.
•If downstream devices are not successfully identified, the H2TU-C reports four-character status messages. The H2TU-C attempts communication again and reports four-character status messages. The H2TU-C repeats this cycle until a downstream device is detected.
3Verify that the remote unit synchronizes normally. The H2TU-C status LED should light a steady green, and the front-panel display should report normal margin messages.
4Verify that a valid DS1 signal has been applied to the H2TU-C and the H2TU-R.
•If no DS1 signal is being applied to either the H2TU-C or the H2TU-R inputs, then the appropriate DS1 alarms (LLOS or RLOS) are observed on the front-panel display, and the status LED flashes red.
•If a valid DS1 signal is being supplied to the H2TU-C and H2TU-R, then DS1 alarm indications should be absent and the status LED should be a steady green.