152-388-100-02, Issue 2

Provisioning

 

 

PROVISIONING

There are two provisioning methods:

Use the MODE and SEL buttons on the front panel of the H2TU-C to:

Set system options

Reset the H2TU-C to its factory default settings for system options

Display system option settings (scroll mode)

Select system loopbacks

Use a maintenance terminal (VT100 terminal or a PC running terminal emulation software) connected to the H2TU-C craft port (or to an HMU craft port) to access the HiGain HDSL2 maintenance screens (Figure 3 on page 12). This gives you full access to all H2TU-C status, history, inventory, and provisioning screens.

No dip switches or jumpers are required to provision the H2TU-C-388 List 1 as it contains a non-volatile RAM (NVRAM) which stores the system option settings. System option settings are retained if shelf power is lost or if the H2TU-C-388 List 1 is unplugged.

USING THE MODE AND SEL BUTTONS

Setting Options through MODE and SEL

To provision the H2TU-C-388 List 1 through the MODE and SEL buttons on the front panel:

1Press the MODE button for 1 second and then release it. The front panel display alternately shows the first system parameter and its current setting.

2Press the SEL button to step through all possible settings of the selected parameter.

3After the desired setting has been selected, press the MODE button. This updates the current displayed parameter to the selected setting, then advances to the next configurable parameter. After the last parameter has been selected, a CONF NO message appears on the front-panel display.

4Do one of the following:

To cancel the session without saving the requested parameter changes, press the MODE button or do nothing. (After 30 seconds, the display returns to its normal mode without saving the new changes.)

To accept the requested parameter changes, press the SEL button. (A CONF YES message displays, and the display returns to its normal mode after saving the new changes.)

H2TU-C-388 List 1

June 6, 2000

9