American Power Conversion VT ISX manual Operation Procedures

Models: VT ISX

1 36
Download 36 pages 25.44 Kb
Page 21
Image 21
Operation Procedures

Operation Procedures

Turn into mechanical bypass using the Mechanical Bypass Lever

The load is not protected by the UPS when the internal mechanical bypass system is active, and, the power is not conditioned.

Caution

If the UPS is running and controllable through the display, carry out steps 1 through 5. If not, go directly to step 4.

Note

Control

Display

Status

Diags

Setup

Help

Logging

 

Main Menu

From the Main Menu, select Control and press ENTER

Use UP/DOWN key to navigate to UPS into Bypass and press ENTER

Use UP/DOWN key to navigate to YES, confirm UPS into bypass, and press ENTER

Remove UPS Front Panel

!

Output

Pwr

Zone

 

 

 

 

Probe

10/100Base-T

 

Reset

 

 

 

 

 

 

10/100

 

 

AP9619

Network Management Card EM

 

 

 

 

 

 

 

 

 

 

 

BATTERY UNIT

 

 

 

 

BATTERY UNIT

 

 

 

 

BATTERY UNIT

 

 

 

 

BATTERY UNIT

Turn the Mechanical Bypass Lever upwards to activate the internal mechanical bypass switch. The load will now be supported directly by mains power.

990-2820A

Smart-UPS® ISX 30-40 kVA, 400V Operation

15

Page 21
Image 21
American Power Conversion VT ISX manual Operation Procedures, Turn into mechanical bypass using the Mechanical Bypass Lever