Operation Procedures
Turn into mechanical bypass using the Mechanical Bypass Lever
The load is not protected by the UPS when the internal mechanical bypass system is active, and, the power is not conditioned.
Caution
If the UPS is running and controllable through the display, carry out steps 1 through 5. If not, go directly to step 4.
Note
Control | Display |
Status | Diags |
Setup | Help |
Logging |
|
Main Menu
From the Main Menu, select Control and press ENTER
Use UP/DOWN key to navigate to UPS into Bypass and press ENTER
Use UP/DOWN key to navigate to YES, confirm UPS into bypass, and press ENTER
Remove UPS Front Panel
! | Output | Pwr | Zone |
|
|
|
| Probe | |
| Reset |
|
|
|
|
|
|
| 10/100 |
|
| AP9619 | Network Management Card EM | |
|
|
| ||
|
|
|
| |
|
|
|
| BATTERY UNIT |
|
|
|
| BATTERY UNIT |
|
|
|
| BATTERY UNIT |
|
|
|
| BATTERY UNIT |
Turn the Mechanical Bypass Lever upwards to activate the internal mechanical bypass switch. The load will now be supported directly by mains power.