Configuration – Connection of Load to the PDU
Disconnecting load from the PDU(s)
To disconnect the load, set the applicable breaker(s) to the OFF position.
PDU output breaker ratings
|
|
| Nominal breaker rating |
| |
Rear of unit | Ambient temperature in front of unit ºC | 16 | 32 | 40 | 50 |
|
|
|
|
|
|
Free exhaust | 20 | 16 | 32 | 40 | 50 |
Free exhaust | 30 | 14.4 | 30.4 | 38 | 47.5 |
Free exhaust | 40 | 12.8 | 27.2 | 34 | 42.5 |
Hot aisle | 25 | 14.4 | 30.4 | 38 | 47.5 |
containment |
|
|
|
|
|
|
|
|
|
|
|