Image 25

Configuration – Connection of Load to the PDU

Disconnecting load from the PDU(s)

To disconnect the load, set the applicable breaker(s) to the OFF position.

PDU output breaker ratings

 

 

 

Nominal breaker rating

 

Rear of unit

Ambient temperature in front of unit ºC

16

32

40

50

 

 

 

 

 

 

Free exhaust

20

16

32

40

50

Free exhaust

30

14.4

30.4

38

47.5

Free exhaust

40

12.8

27.2

34

42.5

Hot aisle

25

14.4

30.4

38

47.5

containment

 

 

 

 

 

 

 

 

 

 

 

990-2820A

Smart-UPS® ISX 30-40 kVA, 400V Operation