External Connection

NOTICE!

Check correct phase rotation of mains input voltage!!

Max. input/output cables: 120mm2. Battery: 70 mm2.

If there is no neutral input Dzn0 or Dyn11 input isolation transformer is required.

UPS

External

External

External PE

Maximum

External

 

Input

Input Cable

Cable

External

Output

 

Fuses* FM

[mm2]

[mm2]

Output

Cable

 

[A]

380-415V

 

Fuses*

[mm2]

 

380-415V

 

 

[A]

 

 

 

 

 

 

 

40kW

80

25

16

63

16

 

 

 

 

 

 

*DIN gL types

NOTICE!

All cable dimensions are recommended sizes only. Refer to local legal regulations.

UPS

External Alarm

External System

External Battery

External

 

Cable max.

Earth Cable

Breaker

Battery Cable

 

[mm2]

[mm2]**

[A]

[mm2]

 

 

 

 

 

40KW

2

10

63

16

 

 

 

 

 

PVC cables isolated to withstand ambient temperature of max. 30oC.

** Must be rated as external PE cable if mains system is not supplying PE.

NOTICE!

Install gland plate in bottom of unit.

990-4050

16

Installation Guide APC Silcon 10-40kW 400V UPS

Page 16
Image 16
APC 10-40KW 400V UPS manual Mm2 Output Cable, Fuses