3.0Installation

3.1Requirements on Site

All system parts are accessible from front or top of UPS. Cable entries are accessible from bottom. A 1m free space on all sides should be allowed during installation. Once the system is installed it may be placed close to walls as long as free space is allowed for system doors to open. (Per applicable national and/or local codes.)

For ventilation and service purposes allow for free space of minimum 1m above the unit or per national and/or local codes and in front of UPS. Never install systems in direct sunlight.

NOTICE!

For reliability reasons do not stand on the UPS. keep the UPS cabinet surface free of any objects.

3.1.1 Cabinet Dimensions H*xWxD - 1400xWx800 [mm]. Width as in below table:

* H is 1500 mm for optional IP31 cabinets

 

Width

Width With Built-in Batteries

Width for Separate

 

Without

 

[mm]

 

Battery Cabinets

 

Batteries

 

 

 

[mm]

 

[mm]

 

 

 

 

 

 

 

 

 

 

 

 

UPS

 

1xBP I*

2xBP I*

3xBP I*

1xBP II**

1xBP III***

 

 

 

 

 

 

 

10kW

600

600

800

1000

1x800

1x1000

 

 

 

 

 

 

 

20kW

600

600

800

1000

1x800

1x1000

 

 

 

 

 

 

 

40kW

600

 

1000

 

1x800

1x1000

 

 

 

 

 

 

 

*BP I = Battery Pack I = 1 x 64 x 7 Ah batteries

**BP II = Battery Pack II = 1 x 64 x 24Ah batteries

***BP III = Battery Pack III = 1 x 64 x 38 Ah batteries

990-4050

8

Installation Guide APC Silcon 10-40kW 400V UPS