Options/Accessories

H002a

6.2.5 Switching Back to Normal Parallel/Redundant Operation

1.Turn input switch (Q001) and output switch (Q002) to position “1”

2.Charge capacitor, connect battery and start up UPS

UPS will automatically switch to normal operation and start load-sharing with other parallelled UPS(s).

WARNING!

System will discharge built-in capacitors, but check terminal voltage before proceding.

990-4050

Installation Guide APC Silcon 10-40kW 400V UPS

67

Page 67
Image 67
APC 10-40KW 400V UPS manual Switching Back to Normal Parallel/Redundant Operation