External Connection

4.7.1 Cabinets

UPS with Built-in Batteries

4.7.2 Preparing Batteries

CAUTION!

Battery drawer weighs approx. 22 kg with batteries.

The 12V, 7.2 Ah batteries are glued to drawer plate.

Battery drawers present a risk of electric shocks. Prior to installation of battery drawers, remove conductive jewellery such as chains, watches and rings. High-voltage short-circuits through conductive materials may cause severe burns.

Do not install battery drawers in UPS frame until all AC/DC sources are disconnected.

If battery drawers need to be stored for extended periods, store in a dry, cool environment.

Keep battery drawers in an upright position.

Do not stack more than 3 cardboard-wrapped battery drawers on top of each other.

990-4050

Installation Guide APC Silcon 10-40kW 400V UPS

33

Page 33
Image 33
APC 10-40KW 400V UPS manual Cabinets, Preparing Batteries