Options/Accessories

6.7.1 Connecting Isolation Transformer

NOTICE!

If an MCCB is used in stead of external input fuses, the MCCB load capacity must be 8xIn (nominal current) for minimum 10 ms.

Isolation

External

External

External PE

External

External

Transformer

Input Fuses*

Input Cable

Cable [mm2]

Output

Temp.

 

FM [A]

[mm2]

 

Cable

Signal

 

380-415V

380-415V

 

[mm2]

Cable max.

 

 

 

 

 

[mm2]

 

 

 

 

 

 

10kW

20

4

4

4

2

 

 

 

 

 

 

20kW

40

10

10

10

2

 

 

 

 

 

 

40kW

80

25

16

25

2

 

 

 

 

 

 

*DIN gL types

PVC cables isolated to withstand a maximum ambient temperature of 30oC.

990-4050

Installation Guide APC Silcon 10-40kW 400V UPS

79

Page 79
Image 79