External Connection

4.8.1 Battery Breaker Box

UPS

Ampere

Connection

Max.

Dimensions

Weight

 

Rating

Cable

short-

HxWxD [mm]

[kg]

 

[A]

[mm2]

circuit

 

 

 

 

 

current [kA]

 

 

 

 

 

 

 

 

10 kW

25

4

10

540x540x183

20

20 kW

50

10

10

504x540x183

20

40 kW

63

16

10

540x540x183

20

 

 

 

 

 

 

990-4050

Installation Guide APC Silcon 10-40kW 400V UPS

41

Page 41
Image 41
APC 10-40KW 400V UPS manual Battery Breaker Box, Ampere Connection Max Dimensions Weight Rating Cable Short, 20 kW, 40 kW