System Specifications

7.0System Specifications

7.1Technical Data

 

Voltage

3x380/400/415V

 

 

 

Input

Voltage tolerance

+15%

 

Normal operation

+10% (standard)

 

Bypass operation

+4, 6, 8% (programmable)

 

 

 

 

Frequency

50Hz/60Hz

 

 

+6 standard

 

 

+0.5-8% (programmable)

 

 

 

 

Input power factor

load 25% minimum 0.97

 

 

load 100% minimum 0.99

 

 

 

 

Current distortion

Max. 5%

 

 

 

Output

Voltage

3x380/400/415V

 

 

 

 

Voltage tolerance

+1% static symmetrical load

 

 

+3% static symmetrical load

 

 

+5% 0-100% load step

 

 

 

 

Voltage distortion

max. 3% linear load

 

 

max. 5% non-linear load

 

 

 

 

Load power factor

0.9 lead to 0.8 lag

 

 

 

 

Frequency

50Hz/60Hz (mains synchronized)

 

 

+0.1% free-running

 

 

 

 

Overload capacity

 

 

Mains operation

200% - 60 seconds

 

Mains operation

125% - 10 minutes

 

Battery operation

150% - 30 seconds

 

Bypass operation

125% - continuous

 

 

 

General

Ambient temperature

0-40oC (Temperatures above 25oC will

 

 

reduce battery lifetime)

 

 

 

 

Humidity

Max. 95% non-condensing

 

Protection class

IP30

 

Safety

EN 50091-1

 

 

CE Mark

 

Emission and Immunity

EN 50091-2

 

Static bypass switch

Built-in

 

Auto restart

Programmable

 

Economy mode

Programmable

 

 

 

7.2Back-up Time / Dimensions / Weigh

Type

 

10kW

 

 

20kW

 

 

40kW

 

 

 

 

 

 

 

 

 

 

Back-up time.

22 min.

50 min.

78 min.

8

22

35

0

 

8

UPS with built-

 

 

 

min.

min.

min.

min.

 

min.

in batteries

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Height [mm]

1400

1400

1400

1400

1400

1400

1400

 

1400

 

 

 

 

 

 

 

 

 

 

Width [mm]

600

800

1000

600

800

1000

600

 

1000

 

 

 

 

 

 

 

 

 

 

Depth [mm]

800

800

800

800

800

800

800

 

800

 

 

 

 

 

 

 

 

 

 

Weight [kg]

385

550

755

400

585

765

285

 

650

 

 

 

 

 

 

 

 

 

 

990-4050

86

Installation Guide APC Silcon 10-40kW 400V UPS

Page 86
Image 86
APC 10-40KW 400V UPS manual System Specifications, Technical Data, Back-up Time / Dimensions / Weigh