External Connection

4.8.3 Fuse-box

UPS

Ampere Rating

Connection

Max.

Dimensions

Weight

 

[A]

Cable [mm2]

short-circuit

HxWxD [mm]

[kg]

 

 

 

current [kA]

 

 

 

 

 

 

 

 

10 kW

25

4

10

540x540x183

20

20 kW

50

10

10

504x540x183

20

40 kW

63

16

10

540x540x183

20

 

 

 

 

 

 

990-4050

Installation Guide APC Silcon 10-40kW 400V UPS

43

Page 43
Image 43