Options/Accessories

6.6.2Remote Display Installation 6.6.2.1Connecting RS232C and Mains Adapter

CAUTION!

Wiring for alarm and signal circuit field to be rated 300V (minimum).

Rear view

Rear view

Front view

1. Turn 180° to loosen the 4 screws

2. Remove front cover

3.

Mont back plate

Cable entry from bottom and rear

DP9-F

Mains adapter

 

 

 

4.

Connect cables

 

 

 

6.6.2.2Remote Display Power Supply

The remote display is supplied by normal AC power with no battery back-up. For UPS data transmission to remote display to remain unaffected during power failure, the remote display must be supplied from an uninterruptible power source.

Converters used to extend communication distance must also be supplied from uninterruptible power sources.

6.6.2.3 Remote Display Cables

RS232C to RS232C cable:

APC Silcon, DB25-F

Remote Display, DB9-M

X

Connect shield at one end only!

Rating: Refer to Local/National electrical codes.

Communication voltage +15VDC

990-4050

76

Installation Guide APC Silcon 10-40kW 400V UPS

Page 76
Image 76
APC 10-40KW 400V UPS manual 2.2Remote Display Power Supply, Remote Display Cables