Installation and Operator’s Manual

Page 51 of 63

(PVI-3600-OUTD-UK-F-W Rev.: 1.0)

 

 

 

6.3Display menù

When using PLM or the RS-485 serial link communication each unit must have a unique address. The default address of each unit is 2. When connecting multiple units on the same serial or PLM link a new address needs to be assigned to each unit to avoid communication errors.

6.4Address Information

Addresses 0 is reserved for the host computers; addresses 1 is reserved for the automatic addressing mode.

The RS-485 serial link uses addresses 2 thru 33. The PLM link uses addresses 2 thru 63.

6.5Manual address setting

Use the following procedure to set the new address:

1)Press the key on the side of the LCD display button for at least 5 seconds.

2)AURORA disconnects from the grid, the yellow LED begins to blink and the display shows:

NEW ADDRESS

#####

3)The first address is 2. Press the key as many times as needed to select the address between 2 and 63. After the number 63 there is the AUTO address. Continuing with the Key press, the address starts back from 2. In order to scroll the address number press the key for a short while (less than 5 sec.).

WARNING: The user must NOT select the address AUTO. The automatic setting of addresses through this key is a feature used on multiple wind turbine installations by factory authorized personnel using

special software.

Page 51
Image 51
Aurora Electronics PVI-3600-OUTD-UK-F-W manual Display menù, Address Information, Manual address setting