Installation and Operator’s Manual

Page 52 of 63

(PVI-3600-OUTD-UK-F-W Rev.: 1.0)

 

 

 

2

3

63. AUTO

4) Confirm the choice by pressing once more the key for at least 5 seconds.

NOTE: When using RS-485 link there can be no more than 31 inverters connected on the same link. Although you are free to choose any address between 2 and 63 it is recommended that you use addresses between 2 and 33 for the RS-485 serial link.

NOTE: When using RS-485 link, in case one or more inverters are later added to the system, please remember to switch back to the OFF position the dip-switch of the former last inverter of the system.

6.6Automatic setting

The key AUTO activates the channel to select the addresses. Only Factory authorized personnel are able to perform this procedure.

6.7Verifying the paralleled input configuration.

The inverter is configured at the factory for parallel inputs. The selected configuration can be verified through the display.

1)Once defined the inverter address, per the procedure described in § 6.5 and 6.6, press the key on the right of the display for longer than 5 sec. in order to proceed the next screen.

NEW ADDRESS 2

Page 52
Image 52
Aurora Electronics PVI-3600-OUTD-UK-F-W manual Automatic setting, Verifying the paralleled input configuration