2.3 #AA

Description : Read Analog Input

Syntax : #AA[CHK](cr)

#delimiter character

AAaddress of reading module(00 to FF) Response : Valid Command : >(Data)[CHK](cr)

Syntax error or communication error may get no re- sponse.

>delimiter for valid command

(Data) analog input value, reference Sec.1.10 for its format. For I-7018/18P, the data is the combination for each chan-

nel respectively.

 

Example :

 

Command : #01

Receive : >+02.635

Read address 01, return data success.

Command : #02

Receive : >4C53

Read address 02, return data in HEX format success. Command : #04

Receive : >+05.123+04.153+07.234-02.356+10.000- 05.133+02.345+08.234

Module address 04 is I-7018. Read address 04, get analog input data of 8 channels.

Related Command :

Sec.2.1 %AANNTTCCFF, Sec.2.7 $AA2

Related Topics :

Sec.1.10 Configuration Tables

24

I-7011, I-7018 User Manual