2.37 ~AA4

Description : Read PowerOn Value and Safe Value

Syntax : ~AA4[CHK](cr)

~delimiter character

AA

address of reading module (00 to FF)

4

command for reading PowerOn Value and Safe Value

Response : Valid Command :

!AAPPSS[CHK](cr)

 

Invalid Command :

?AA[CHK](cr)

 

Syntax error or communication error may get no re-

 

sponse.

 

!

delimiter for valid command

 

?delimiter for invalid command

AA address of response module(00 to FF)

PPPowerOn Value, 00=DO0 off,DO1 off, 01=DO0 on,DO1 off, 02=DO0 off, DO1 on, 03=DO0 on, DO1 on

SSSafe Value, data format is same as PP Example :

Command : ~014Receive : !010000

Read address 01 PowerOn/Safe Value, return PowerOn Value is DO0 off, DO1 off, Safe Value is DO0 off, DO1 off.

Related Command :

Sec.2.38 ~AA5PPSS

Related Topic :

Sec.3.2 Module Status, Sec.3.3 Dual Watchdog Operation Note : The command is for I-7011/11D/11P/11PD only

Rev:B1.0

I-7011, I-7018 User Manual