2.37 ~AA4
Description : Read PowerOn Value and Safe Value
Syntax : ~AA4[CHK](cr)
~delimiter character
AA | address of reading module (00 to FF) | |
4 | command for reading PowerOn Value and Safe Value | |
Response : Valid Command : | !AAPPSS[CHK](cr) | |
| Invalid Command : | ?AA[CHK](cr) |
| Syntax error or communication error may get no re- | |
| sponse. |
|
! | delimiter for valid command |
|
?delimiter for invalid command
AA address of response module(00 to FF)
PPPowerOn Value, 00=DO0 off,DO1 off, 01=DO0 on,DO1 off, 02=DO0 off, DO1 on, 03=DO0 on, DO1 on
SSSafe Value, data format is same as PP Example :
Command : ~014Receive : !010000
Read address 01 PowerOn/Safe Value, return PowerOn Value is DO0 off, DO1 off, Safe Value is DO0 off, DO1 off.
Related Command :
Sec.2.38 ~AA5PPSS
Related Topic :
Sec.3.2 Module Status, Sec.3.3 Dual Watchdog Operation Note : The command is for
Rev:B1.0 | 59 |