B&B Electronics I-7011 user manual 38 ~AA5PPSS, Syntax ~AA5PPSSCHKcr

Models: I-7011

1 64
Download 64 pages 6.36 Kb
Page 60
Image 60

2.38 ~AA5PPSS

Description : Set PowerOn Value and Safe Value

Syntax : ~AA5PPSS[CHK](cr)

~delimiter character

AA

address of setting module (00 to FF)

5

command for setting PowerOn Value and Safe Value

PPPowerOn Value, 00=DO0 off, DO1 off, 01=DO0 on, DO1 off, 02=DO0 off, DO1 on, 03=DO0 on, DO1 on

SS

Safe Value, data format is same as PP

Response : Valid Command :

!AA[CHK](cr)

 

Invalid Command :

?AA[CHK](cr)

 

Syntax error or communication error may get no re-

 

sponse.

 

!

delimiter for valid command

 

?delimiter for invalid command

AAaddress of response module(00 to FF) Example :

Command : ~0150003 Receive : !01

Set address 01 PowerOn Value is DO0 off, DO1 off, Safe Value is DO0 on, DO1 on, return success.

Related Command :

Sec.2.37 ~AA4

Related Topic :

Sec.3.2 Module Status, Sec.3.3 Dual Watchdog Operation Note : The command is for I-7011/11D/11P/11PD only

60

I-7011, I-7018 User Manual

Rev:B1.0

Page 60
Image 60
B&B Electronics I-7011 user manual 38 ~AA5PPSS, Syntax ~AA5PPSSCHKcr