2.38 ~AA5PPSS
Description : Set PowerOn Value and Safe Value
Syntax : ~AA5PPSS[CHK](cr)
~delimiter character
AA  | address of setting module (00 to FF)  | 
5  | command for setting PowerOn Value and Safe Value  | 
PPPowerOn Value, 00=DO0 off, DO1 off, 01=DO0 on, DO1 off, 02=DO0 off, DO1 on, 03=DO0 on, DO1 on
SS  | Safe Value, data format is same as PP  | |
Response : Valid Command :  | !AA[CHK](cr) | |
  | Invalid Command :  | ?AA[CHK](cr) | 
  | Syntax error or communication error may get no re-  | |
  | sponse.  | 
  | 
!  | delimiter for valid command  | 
  | 
?delimiter for invalid command
AAaddress of response module(00 to FF) Example :
Command : ~0150003 Receive : !01
Set address 01 PowerOn Value is DO0 off, DO1 off, Safe Value is DO0 on, DO1 on, return success.
Related Command :
Sec.2.37 ~AA4
Related Topic :
Sec.3.2 Module Status, Sec.3.3 Dual Watchdog Operation Note : The command is for 
60  | Rev:B1.0 |