2.29 @AARL

Description : Read Low Alarm

Syntax : @AARH[CHK](cr)

@delimiter character

AA

address of reading module (00 to FF)

RL

command for reading low alarm

Response : Valid Command :

!AA(Data)[CHK](cr)

 

Invalid Command :

?AA[CHK](cr)

 

Syntax error or communication error may get no re-

 

sponse.

 

!

delimiter for valid command.

 

?delimiter for invalid command.

AA

address of response module(00 to FF)

(Data)

low alarm value in engineer unit format.

Example :

 

Command : @01RL

Receive : !01-2.5000

Read address 01 low alarm, return -2.5000.

Related Command :

Sec.2.25 @AALO(Data)

Related Topic :

Sec.3.6 High/Low Alarm

Note : The command is for I-7011/11D/11P/11PD only

Rev:B1.0

I-7011, I-7018 User Manual

51