2.19 ~AAO(Data)

Description : Set Module Name

Syntax : ~AAO(Data)[CHK](cr)

~delimiter character

AA

address of setting module (00 to FF)

O

command for setting module name

(Data)

new name for module, max 6 characters

Response : Valid Command :

!AA[CHK](cr)

 

Invalid Command :

?AA[CHK](cr)

 

Syntax error or communication error may get no re-

 

sponse.

 

!

delimiter for valid command

 

?delimiter for invalid command

AAaddress of response module(00 to FF) Example :

Command : ~01O7018

Receive : !01

Set address 01 module name to 7018, return success.

Command : $01M

Receive : !017018

Read address 01 module name, return 7018. Related Command :

Sec.2.17 $AAM

40

I-7011, I-7018 User Manual

Rev:B1.0