2.24 @AAHI(Data)

Description : Set High Alarm

Syntax : @AADI[CHK](cr)

@delimiter character

AA

address of setting module (00 to FF)

HI

command for setting high alarm value

(Data)

high alarm values, data format is in engineer unit format.

Response : Valid Command :

!AA[CHK](cr)

 

Invalid Command :

?AA[CHK](cr)

 

Syntax error or communication error may get no re-

 

sponse.

 

!

delimiter for valid command

 

?delimiter for invalid command

AAaddress of response module(00 to FF) Example :

Command : @01HI+2.5000 Receive : !01

Set address 01 high alarm +2.5000, return success. Related Command :

Sec.2.23 @AAEAT, Sec.2.28 @AARH Related Topic :

Sec.3.6 High/Low Alarm

Note : The command is for I-7011/11D/11P/11PD only

46

I-7011, I-7018 User Manual

Rev:B1.0

Page 46
Image 46
B&B Electronics I-7011 user manual 24 @AAHIData