2.28 @AARH
Description : Read High Alarm
Syntax : @AARH[CHK](cr)
@delimiter character
AA | address of reading module (00 to FF) | |
RH | command for reading high alarm | |
Response : Valid Command : | !AA(Data)[CHK](cr) | |
| Invalid Command : | ?AA[CHK](cr) |
| Syntax error or communication error may get no re- | |
| sponse. |
|
! | delimiter for valid command. |
|
?delimiter for invalid command.
AA | address of response module(00 to FF) | |
(Data) | high alarm value in engineer unit format. | |
Example : |
| |
Command : @01RH | Receive : !01+2.5000 |
Read address 01 high alarm, return +2.5000. Related Command :
Sec.2.24 @AAHI(Data)
Related Topic :
Sec.3.6 High/Low Alarm
Note : The command is for
50 | Rev:B1.0 |