2.28 @AARH

Description : Read High Alarm

Syntax : @AARH[CHK](cr)

@delimiter character

AA

address of reading module (00 to FF)

RH

command for reading high alarm

Response : Valid Command :

!AA(Data)[CHK](cr)

 

Invalid Command :

?AA[CHK](cr)

 

Syntax error or communication error may get no re-

 

sponse.

 

!

delimiter for valid command.

 

?delimiter for invalid command.

AA

address of response module(00 to FF)

(Data)

high alarm value in engineer unit format.

Example :

 

Command : @01RH

Receive : !01+2.5000

Read address 01 high alarm, return +2.5000. Related Command :

Sec.2.24 @AAHI(Data)

Related Topic :

Sec.3.6 High/Low Alarm

Note : The command is for I-7011/11D/11P/11PD only

50

I-7011, I-7018 User Manual

Rev:B1.0

Page 50