2.18 $AAZ(Data)

Description : Set LED Data

Syntax : $AAZ(Data)[CHK](cr)

$

delimiter character

 

AA

address of setting module (00 to FF)

Z

command for setting LED data

(Data)

data for show on the LED, from -19999. to +19999. The

 

data need sign, 5 digits and decimal point.

Response : Valid Command :

!AA[CHK](cr)

 

Invalid Command :

?AA[CHK](cr)

 

Syntax error or communication error may get no re-

 

sponse.

 

!

delimiter for valid command

 

?delimiter for invalid command or LED not set to host control

AAaddress of response module (00 to FF) Example :

Command : $01Z+123.45 Receive : !01

Send address 01 LED data +123.45, return success.

Command : $02Z+512.34 Receive : ?02

Send address 02 LED data +512.34, return the LED is not setting in the host mode.

Related Command :

Sec.2.12 $AA8, Sec2.13 $AA8V

Note : The command is for I-7011D/11PD only

Rev:B1.0

I-7011, I-7018 User Manual

39

Page 39
Image 39
B&B Electronics I-7011 user manual 18 $AAZData, Syntax $AAZDataCHKcr