D9112B | Program Entry Guide | 1.0 Panel Wide Parameter EN | 11
Bosch Security Systems | 2/04 | 74-06145-000-D
User ID 5 = ZONE F
User ID 6 = ZONE 6
User ID 7 = ZONE 7
User ID 8 = ZONE 8
User ID 91 = ZONE 1
User ID 92 = ZONE 2
User ID 93 = ZONE 3
User ID 94 = ZONE 4
User ID 95 = ZONE 5
User ID 96 = ZONE 0
COMMAND 1 = ZONE 9 (only closing)
D6500 Receiving BFSK Format: Opening/closing
User ID numbers are identified at the receiver as ZN
(same identification as independent points). The ZN
numbers are based on the “tens” digit of the User ID
number.
DTMF Dialing
Use DTMF (dual-tone multi-frequency) to dial the
central station receiver phone number(s) for event
reports, and/or the D5300 Remote Account
Manager.
Default: Yes
Selection: Yes or No
Yes Dials the programmed phone
number(s) using DTMF.
No Pulse dialing only
Phone Supv Time
Sets the amount of time the panel continues to
monitor a faulted phone line before initiating phone
line trouble responses.
Default: Blank
Selection: Blank or 10 to 240
Blank No phone line supervision.
10 to 240 Initiate phone line trouble response if
the phone line continues to be faulted
after the programmed amount of
seconds expire. After a faulted phone
line restores, it takes the same amount
of time to initiate restoral responses.
Make settings in ten sec. increments.
Phone line trouble responses:
Command centers display SERVC PH LINE # and
sound the trouble tone.
Restoral
reports identify the previously failed line
after it restores when a single phone line is used, if
Power/Phone
is enabled in Phone Routing.
Trouble and restoral events are reported if
Power/Phone
is enabled in Phone Routing, a Dual
Phone Line Module is installed, and one of the
phone lines is operational.
Alarm On Fail
Default: Yes
Selection: Yes or No
Yes Generate alarm responses in Area 1
and trouble responses in all other areas
when a phone line fails.
Phone Supv Time
must be programmed to use this
feature.
Phone Failure Alarm Responses: An
alarm tone sounds at command centers
assigned to Area 1. The alarm bell
relay for Area 1 activates. The
Phone Fail relay activates if programmed in
Relay Parameters.
No Trouble responses when a phone line
fails.
Phone Supv Time must be
programmed to use this feature.
Two Phone Lines
Use when a Dual Phone Line Module is connected
to the D9112. Both lines must operate the same,
either ground start or loop start. NFPA standards
prohibit the use of ground start phone lines in
systems monitoring fire points.
Default: No
Selection: Yes or No
Yes Dual Phone Line Module installed.
The LEDs on the module light to
indicate primary or secondary line
trouble and Comm Fail.
No No Dual Phone Line Module.
0101
0101
0101
IMPORTANT! Program Phone Supv Time
when using two phone lines.