P## Bypassable
Bypass and force arm the point. Points can be bypassed by entering the Bypass a Point function at a command
center, a RAM II command, or a “Bypass a Point” SKED.
To automatically return a bypassed point to the system when disarming, program
Returnable YES. Otherwise,
you can use Unbypass a Point (Command 00), RAM II UNBYPASS command, or “Unbypass a Point” SKED.
When a controlled point is force armed, it can return to the system when the fault clears if
Returnable is
programmed YES. If it is not returnable, the point stays out of the system until the area is disarmed.
If the panel is reset while a point is bypassed, a
Restoral
report is not sent when the point is unbypassed and it
returns to normal.
Default: No
Selection: Yes or No
Yes This point can be bypassed and force armed.
Note:
24-hour points can be bypassable, but the application should be carefully considered.
Buz on Fault and
Report Bypass at Occurrence
should be YES for bypassable 24-hour points.
When a 24-hour point is bypassed, the report should be sent as it occurs. If the area does not send a
Closing report, a Deferred Bypass report is not sent.
Instead of programming a bypassable 24-hour point, consider a bypassable perimeter point type with a
Point Response
of 9 to D. 24-hour points do not show faults or bypasses when an arming command is
entered, but perimeter points do.
No This point cannot be bypassed or force armed from the command center or RAM II. However, it
can be force armed by automatic arming at the end of the closing window (see Opening & Closing
Auto Close) or by a Sked programmed to arm the area.
P## Swinger Bypass
Automatically bypass a point if it generates four
alarms or four troubles during one clock hour (for
example, between 2:00 and 2:59). If the point has a
partial count (less than four events during an hour),
the count is reset to zero on the hour.
To return a swinger bypass point to the system:
disarm the area, use the Unbypass a Point
(Command 00) function, send the RAM II unbypass
command, or execute an “Unbypass a Point” Sked.
When a point is bypassed because of a swinger
condition, a
Swinger Bypass report is sent.
Default: No
Selection: Yes or No
Yes Enable Swinger Bypass for this point.
No Disable Swinger Bypass for this point.
P## Report Bypass at Occurrence
Generate a
Command Bypass
report as soon as it is
bypassed. This option should be enabled for all
bypassable 24-hour points. You may also elect to
report bypassed 24 –hour points at the time the area
is armed. See
Defer Bypass report.
Default: No
Selection: Yes or No
Yes Send a
Command Bypass
report at
the time the point is bypassed.
No Do not send
Command Bypass
at the
time the point is bypassed.