7 Point Open/Close with a D279: Used for Point Arming and Disarming.
Point Response
must be
programmed 1. Local bells are silenced through the command center (to have bell control at the
D279 see
Point Index
entry 4).
Cut the W1 jumper on the D279 to send
Point Opening
and
Point Closing
reports. If the D279’s
W1 jumper is NOT cut then no
Open
or
Close
report is sent, regardless of the D9112
programming.
Normal: The point is armed and sends
Point Closing
.
Point Closing
is not sent if
Local Alarm
is
YES.
Open: The point is disarmed and sends a
Point Opening
.
Point Opening
is not sent if
Local
Armed
is YES.
Short: A short is an alarm condition.
Alarm
and
Restoral
reports are not sent if
Local Disarmed
is YES.
P## Pt Response
Default: See
Program Record Sheet
Selection: 0 to D
Point Response defines the “Point Response to Opens and Shorts” for this point. Table 30 show each selection
available for controlled (non-24-Hour) point types and 24-Hour point types.
Table 30: Point Response Table
Pt Response 0 1 2 3 4 5 6 7 8 9 A B C D
Controlled Points:
Armed Open I I I I D D I I D I I I I I
Armed Short I I I I I I D D D I I I I I
Disarmed Open T T T I I T I
Disarmed Short T T T I T I I
24-Hour Points:
Open I T I T I T
Short
I I T T I T
Key: I = Instant Alarm, D = Delayed Alarm, T = Trouble, Blank = no response
0101
0101
0101
Applications for Point response 9 to D
Combine Point Responses 9 to D with Perimeter Point Types to create more flexible 24-hour protection.
Unlike 24-hour points, a faulted perimeter point with a Point Response of 9 to D displays at the command
center when arming. Like a 24-hour point, a point programmed this way can generate alarms whether the
area is armed or disarmed.
Combining Point Response 9 with the Local Disarmed feature provides off-site reporting when the area
is armed, but only local alarm annunciation when the area is disarmed.
Combining Point Response 9 with the Local Armed feature provides off-site reporting when the area is
disarmed, but only local alarm annunciation when the area is armed.