D9112B | Program Entry Guide | 2.0 Area Wide Parameters EN | 26
Bosch Security Systems | 2/04 | 74-06145-000-D
A# Delay Res
Default: No
Selection: Yes or No
Yes
Restoral
report is delayed until the
area bell time expires, and the point
returns to normal.
No
Restoral
reports are sent when point
restores, regardless of bell time.
A# Exit Tone
Default: Yes
Selection: Yes or No
Sound an exit tone during exit delay at command
centers assigned to this area.
A# Exit Dly Time
Default: 60
Selection: 0 to 600
Exit delay time for this area. Select an entry that is a
five sec. increment.
Points programmed for “instant” alarms generate
alarms immediately. Even during exit delay.
Note:
Fail to Close reports require exit delay time: If Fail
To Close in Opening and Closing is programmed
YES, you must enter an exit delay time.
A# Auto Watch
Default: No
Selection: Yes or No
Yes When disarmed, this area automatically goes into watch mode regardless of the status of Watch
Mode before the area is armed.
Automatic Watch does not affect manual Watch Mode toggle. You can still control Watch Mode
using Command 6.
No Watch Mode status is maintained between arm/disarm cycles. If the Watch Mode was ON at the
time the area was armed, it will be ON again when the area is disarmed. If the Watch Mode was
OFF at the time the area is disarmed, it will be OFF when the area is disarmed.
Note:
Watch Mode does not work while the area is perimeter armed.
A# Verify Time
Default: 60
Selection: 10 to 60 sec.
Alarm Verification is designed for use with smoke
detectors to reduce the number of false fire alarms.
When
Verify Time
is programmed, the panel can
double check smoke detector point activations
before generating alarm signals.
Note:
Check with your Authority Having Jurisdiction (AHJ)
to determine the maximum verification time allowed.
Points are programmed individually to activate the
verification feature. See Point Index. Any resettable
fire point can activate alarm verification for the area
to which it is assigned. Bosch Security Systems
recommends the use of separate area alarm-
verification relays.
To enable alarm verification on a point, program
Point Index
Fire Point,
Alarm Verify , and
Resettable as Yes.
When an alarm verification point trips, the D9112
automatically removes power to all resettable points
connected to the areas
Reset Sensors relay. The
sensor reset removes power to the sensors for the
amount of time programmed in
Verify Time
. When
power is reapplied, a 60 sec. confirmation window
begins. If the detector is still in alarm, or trips again
during the confirmation window, or if a different
resettable verification point in the area trips, an
alarm is generated.
Example 1:
Verify Time
is set for 20 seconds. The alarm
verification cycle starts when the detector trips. No
report is generated.