D9112B | Program Entry Guide | 1.0 Panel Wide Parameter EN | 21
Bosch Security Systems | 2/04 | 74-06145-000-D
P## Area Assign
Default: 1
Selection: 1 to 8
Assign each installed printer to an area of the
D9112. This allows the proper routing of events as
determined by the Printer Scope. Assign printers
with Panel Wide scope to Area 1. Assign printers
with Account scope to an area within the account
number you want to record.
System events such as power supervision, passcode
changes, RAM events and such, are only sent to the
printer assigned to AREA 1. To record these events,
make sure a printer is assigned to Area 1 and that
PRT Non Alrm is programmed YES for that
printer.
P ## Supervision
Use this prompt to determine if any responses are
generated when the printer at this address fails. See
the D9131 Printer Interface Operation and Installation
Guide for conditions that are supervised.
Default: No
Selection: Yes or No
Yes No report or local annunciation if this
printer fails.
No Send an
SDI Fail report identifying the
printer address (17, 18, or 19) to the
receiver if this printer fails. (Program
Diagnostic reports for a primary
phone destination in the Phone Routing
Worksheet). Sends a message to all other
printers as non-alarm events. Display
SERVC PRINTER at all command
centers. A relay can be assigned to
indicate printer trouble (see Relay
Assignments).
P## Prt Points
Point events include every event that can be
generated by a point. Events include all of the events
listed in the Fire Alarm/Restoral, Fire Tbl/Rest,
AlarmRest/Cancel, and Trouble logs shown in the
Phone Routing Worksheet.
Default: Yes
Selection: Yes or No
Yes Print point events according to the
Printer Scope and Area Assignment.
All point events are printed on the
local printer regardless of how many
points are programmed.
No Do not print any point events.
P ## Prt O/C
O/C events are all of the events listed in the
Opening and Closing log shown in the Phone Routing
Worksheet.
Default: Yes
Selection: Yes or No
Yes Print Opening and Closing events
according to the Printer Scope and
Area Assignment. All arming and
disarming events are printed on the
local printer regardless of the
programming of any other prompts
associated with openings and closings.
No Do not print any Opening and Closing
events.
P## Prt Non Alrm
Non-Alarm Events are all of the events except Point
events and Opening/Closing events. Non-Alarm
events include all of the events listed in the
Test/Status, Diagnostic, Relay, Skeds, RAM,
Power/Phone, and Service logs shown in the Phone
Routing Worksheet. Information from
Expanded Testreports is not printed when the
Test
report is
generated.
Default: Yes
Selection: Yes or No
Yes Print non-alarm events according to the
Printer Scope and Area Assignment.
No Do not print any non-alarm events.