D9112B | Program Entry Guide | 1.0 Panel Wide Parameter EN | 20
Bosch Security Systems | 2/04 | 74-06145-000-D
Bat Fail/Res Rpt
Determines if battery (DC) power supervision
reports are sent.
The battery must be discharged below 12.1 VDC for
16 sec. before the D9112 responds to a low battery
(see the D9112 Operation and Installation Guide for
discharge schedule).
Default: Yes
Selection: Yes or No

Battery Failure

and

Restoral

reports are sent to the central station. They are routed to the telephone
number programmed for Power/Phone events.
Yes
Modem Reports:
BFSK Reports:
Missing or shorted
Discharged below 12.1 VDC
Missing, shorted, low battery
BATTERY MISSING
BATTERY LOW
TROUBLE ZONE 9
No Battery Failure and Restoral reports are NOT sent to the central station.
Note:
When a battery problem occurs, the trouble buzzer sounds at the command centers unless it is disabled by

AC/Battery

Buzz

(see AC/Battery Buzz).
1.4 Printer Parameters
Up to three D9131 Printer Interface Modules can be
connected to the D9112’s SDI bus. Each printer is
identified by an address of 17, 18, or 19. Options
are available for

Routing

reports and area
assignments.
Printer Address
Default: 17
Selection: 17, 18, or 19
The printer address you are programming.
P## Scope
Press the [SPACE] bar to scroll through the selections. Press [ENT] when the correct selection appears in the
display.
Default: No Printer
Selection: No Printer, Panel Wide, Account, and Area
No Printer Printer disabled
Panel Wide Printer prints all designated events that occur panel-wide. A panel-wide printer crosses account
boundaries.
Account Printer prints all designated events that occur in the area where the printer is assigned and all other
areas that are assigned to the same account. A single account printer displays all the information in
the account but cannot cross boundaries.
Area Printer prints all designated events that occur in the assigned area.