A# Force Armed
Default: Blank
Selection: Blank, 1 to 128, A, B, or C
Activates when the specified area is Force Armed. It
remains activated until the area is disarmed or the
panel is reset. (Perimeter arming and disarming does
not affect this relay.)
A# Watch Mode
Default: Blank
Selection: Blank, 1 to 128, A, B, or C
Activates when a perimeter point is tripped in the
specified area while the area is in Watch Mode. It
remains activated for two seconds.
A# Area Armed
Default: Blank
Selection: Blank, 1 to 128, A, B, or C
This relay activates when the specified area begins
the master arming sequence. The relay remains
activated until the area is disarmed. Entry delay does
not reset this relay.
A typical application for this relay is to control an
“Armed” LED on a keyswitch.
If multiple areas use the same relay, the relay sets
when the last area begins the arming sequence. It
resets when the first area disarms.
A# Area Fault
Default: Blank
Selection: Blank, 1 to 128, A, B, or C
Activates whenever a perimeter or interior point is
faulted. The relay remains activated until all
perimeter and interior points in the area are normal,
bypassed or force armed.
A typical application for this relay is to control a
“faulted point” LED on a keyswitch to indicate that
the area is not ready to arm.
A# Duress
Default: Blank
Selection: Blank, 1 to 128, A, B, or C
Activates when a duress alarm is generated from a
command center assigned the specified area. A
Burg Time must be programmed in Bell Parameters. The
relay provides steady output and remains active until
the bell time expires or the panel is reset.
Duress is a panel-wide function which is enabled in
the Passcode Worksheet. Reporting can be
suppressed by Authority Level.
A# Keypad Fail
Default: Blank
Selection: Blank, 1 to 128, A, B, or C
Activates when a supervised command center
assigned to the area fails (does not respond when the
address is polled). The relay remains activated until
the command center responds. There may be a short
delay between the time the command center fails or
restores and the relay response.
A# Perim Fault
Default: Blank
Selection: Blank, 1 to 128, A, B, or C
Activates when a perimeter point assigned to the
specified area is faulted. This relay activates
regardless of the area’s armed state. This relay
provides a steady output until all perimeter points in
the area are normal, bypassed or force armed.
Any point programmed for
Point Type “1” causes
this relay to respond when the point is opened,
shorted, or missing.
A# Silent Alarm
Default: Blank
Selection: Blank, 1 to 128, A, B, or C
Activates when a point assigned to the specified area
and programmed for
Silent Bell causes an alarm
response.
Burg Time
must be programmed in Bell
Parameters. The relay provides steady output and
remains active until the bell time expires or the
panel is reset.
Point Index
Silent Bell YES, causes this relay to
respond when the point goes into alarm.