D9112B | Program Entry Guide | EN | 85
Bosch Security Systems | 2/04 | 74-06145-000-D
A# Command 7
Default: Blank
Selection: Blank, 1 to 128, A, B, or C
Activates when Command 7 is executed at a
command center assigned to the specified area.
Burg
Time
must be programmed in Bell Parameters. The
relay provides steady output and remains active until
the bell time expires, a valid passcode is entered, or
the panel is reset.
A# Command 9
Default: Blank
Selection: Blank, 1 to 128, A, B, or C
Activates when Command 9 is executed at a
command center assigned to the specified area.
Burg
Time
must be programmed in Bell Parameters. The
relay provides steady output and remains active until
the bell time expires, a valid passcode is entered, or
the panel is reset.
9.2 Panel Wide Relays One relay number can be assigned for each of the
events listed in this section. All areas share the same
relay for these events. Do not use the same relay
number for two different functions.
Printer 17 Fail
Default: Blank
Selection: Blank, 1 to 128, A, B, or C
Activates when Printer 17 (SDI address 17 fails). It
remains active until the printer responds. The printer
must be supervised;
Printer Supervision
in Panel
Wide Parameter must be programmed YES.
Printer 18 Fail
Default: Blank
Selection: Blank, 1 to 128, A, B, or C
Activates when Printer 18 (SDI address 18) fails. It
remains active until the printer responds. The printer
must be supervised;
Printer Supervision
in Panel
Wide Parameter must be programmed YES.
Printer 19 Fail
Default: Blank
Selection: Blank, 1 to 128, A, B, or C
Activates when Printer 19 (SDI address 19) fails. It
remains active until the printer responds. The printer
must be supervised.
Printer Supervision
in
Panel
Wide Parameter
must be programmed YES.
AC Failure
Default: Blank
Selection: Blank, 1 to 128, A, B, or C
Activates when the panel responds to an AC power
failure as programmed in
AC Fail Time
in the
Power Supervision section. It remains active until AC
power is restored.
Buzz on AC/Low Battery Fail
has no effect on this relay.
Battery Trouble
Default: Blank
Selection: Blank, 1 to 128, A, B, or C
Activates when battery voltage falls below 12.1 V or
is missing.
Buzz on AC/Low Battery Fail
has no
effect on this relay.
Phone Fail
Default: Blank
Selection: Blank, 1 to 128, A, B, or C
Activates when a telephone line failure alarm is
generated. (See
Alarm On Fail
in the Phone
programming section.) This relay provides steady
output until a phone line
Restoral
report is sent and
acknowledged by the receiver.
Comm Fail
Default: Blank
Selection: Blank, 1 to 128, A, B, or C
Activates when the panel is unable to communicate
a report. See
Panel Wide Parameters
Phone for an
explanation of Comm Fail. This relay provides
steady output until a report is successfully sent.
Note:
Points can be programmed to be silent alarms that
become audible after two attempts at communicating a
report (see Point Index Audible After 2
Failures). If you use silent points and never want
them to become audible, do not use this relay in
conjunction with an audible device.