Carrier PCV015-060 specifications a50-8493

Models: PCV015-060

1 52
Download 52 pages 34.31 Kb
Page 14
Image 14
a50-8493

Complete C

14

a50-8493

 

 

LEGEND

AL

Alarm Relay Contacts

P1

Field Wiring Terminal Block

BM

Blower Motor

RVS

Reversing Valve Solenoid

BMC

Blower Motor Capacitor

TRANS

Transformer

BR

Blower Relay

TXV

Thermostatic Expansion Valve

CAP

Compressor Capacitor

 

 

 

 

 

 

 

 

 

 

Field Line Voltage Wiring

CB

Circuit Breaker

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Field Low Voltage Wiring

CC

Compressor Contactor

 

 

 

 

 

 

 

 

 

 

CO

Sensor, Condensate Overflow

 

 

 

 

 

 

 

 

 

 

Printed Circuit Trace

FP1

Sensor, Low Temperature Protection, Water Coil

 

 

 

 

 

 

 

 

 

 

Optional Wiring

FP2

Sensor, Low Temperature Protection, Air Coil

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

HP

High-Pressure Switch

 

 

 

 

 

 

 

 

 

 

Relay/Contactor Coil

HPWS

High-Pressure Water Switch

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

JW1

Clippable Field Selection Jumper

 

 

 

 

 

 

 

 

 

 

 

LOC

Loss of Charge Pressure Switch

 

 

 

 

 

 

 

 

 

 

Condensate Pan

LON

Local Operating Network

 

 

 

 

 

 

 

 

 

 

 

MV

Motorized Valve

 

 

 

 

 

 

 

 

 

 

Solenoid Coil

MVES

Motorized Valve End Switch

 

 

 

 

 

 

 

 

 

 

Temperature Switch

NEC

National Electrical Code

 

 

 

 

 

 

 

 

 

 

*Optional Wiring.

Thermistor

Ground

Wire Nut

Relay Contacts - N.C.

Relay Contacts - N.O.

Low Pressure Switch

High Pressure Switch

Splice Cap

Circuit Breaker

NOTES:

1.Compressor and blower motor thermally protected internally.

2.All wiring to the unit must comply with NEC and local codes.

3.Transformer is wired to 460 v BLK/RED lead for 460-3-60 units. Trans- former is energy limiting or may have circuit breaker.

4.FP1 thermistor provides low temperature protection for water. When using antifreeze solutions, cut JW3 jumper.

5.Refer to microprocessor control, LON, or thermostat installation instructions for wiring to the unit. Wire “N01” from LON to “Y1” Com- plete C when a motorized valve is not used. Low voltage wiring must be Class 1 and voltage rating equal to or greater than unit supply voltage.

6.Factory cut JW1 jumper. Dry contact will be available between AL1 and AL2.

7.Transformer secondary ground via green wire with yellow strip from “C” terminal to control box.

8.Fan motors are factory wired for medium speed. For high or low speed, remove BLU wire from fan motor speed tap “M” and connect to “H” for high speed or “L” for low speed.

9.For low speed, remove BLK wire from BR “6” and replace with RED. Connect BLK and BRN wires together.

10.Optional LON wires. Only connect if LON connection is desired at the wall sensor.

11.For blower motors with leads. For medium or low speed, disconnect BLK wire from BR “6”. Connect BLK and ORG/PUR wire together. Connect RED for low or BLU for medium to BR “6”.

12.Blower motor factory wired to medium speed. For low speed remove BLU wire from medium tap and connect to low speed tap. For high speed, remove BLU wire from exisiting speed tap and remove BRN jumper wire from high speed tap. Connect BLU wire to high speed tap. Tape off unconnected end of BRN jumper.

13.The 460-v units using an internal secondary pump will require a neu- tral wire from the supply side in order to feed the accessory with 265-v.

Fig. 16 — 50PCH,PCV Units with Complete C and LON Controller (460 V)

Page 14