Carrier PCV015-060 specifications 50PCH,PCV Unit Physical Data

Models: PCV015-060

1 52
Download 52 pages 34.31 Kb
Page 3
Image 3
Table 1 — 50PCH,PCV Unit Physical Data

or an equivalent protective covering. Cap open ends of pipes stored on the jobsite. This precaution is especially important in areas where painting, plastering, or spraying of fireproof mate- rial, etc. is not yet complete. Foreign material that accumulates within the units can prevent proper start-up and necessitate costly clean-up operations.

Before installing any of the system components, be sure to examine each pipe, fitting, and valve, and remove any dirt or foreign material found in or on these components.

Manual background CAUTION

DO NOT store or install units in corrosive environments or in locations subject to temperature or humidity extremes (e.g., attics, garages, rooftops, etc.). Corrosive conditions and high temperature or humidity can significantly reduce performance, reliability, and service life. Always move units in an upright position. Tilting units on their sides may cause equipment damage.

INSPECT UNIT — To prepare the unit for installation, com- plete the procedures listed below:

1.Compare the electrical data on the unit nameplate with ordering and shipping information to verify that the correct unit has been shipped.

2.Verify that the unit is the correct model for the entering water temperature of the job.

3.Do not remove the packaging until the unit is ready for installation.

4.Verify that the refrigerant tubing is free of kinks or dents, and that it does not touch other unit components.

5.Inspect all electrical connections. Be sure connections are clean and tight at the terminals.

6.Loosen compressor bolts until the compressor rides freely on springs. Remove shipping restraints.

7.Remove the four 1/4 in. shipping bolts from compressor support plate (two bolts on each side) to maximize vibra- tion and sound alternation.

Manual background CAUTION

Failure to remove shipping brackets from spring-mounted compressors will cause excessive noise and could cause component failure due to added vibration.

8.Remove any blower support cardboard from inlet of the blower.

9.Locate and verify any accessory kit located in compressor section.

10.Remove any access panel screws that may be difficult to remove once unit is installed.

Table 1 — 50PCH,PCV Unit Physical Data

50PCH,PCV UNIT

015

 

 

018

 

 

024

 

 

030

 

 

036

 

 

042

 

048

 

 

060

COMPRESSOR (1 each)

 

Rotary

 

 

 

 

 

 

 

 

Scroll

 

 

 

 

 

 

REFRIGERANT TYPE

 

 

 

 

 

 

 

 

 

 

R-410A

 

 

 

 

 

 

Factory Charge (oz)

32

 

 

43

 

 

43

 

 

47

 

 

50

 

 

70

 

74

 

 

82

 

 

 

 

 

 

 

FAN MOTOR AND BLOWER

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fan Motor Type/Speeds

 

 

 

 

 

 

 

 

 

 

PSC/3

 

 

 

 

 

 

Fan Motor (hp)

1/6

 

 

1/6

 

 

1/4

 

 

3/4

 

 

1/2

 

 

3/4

 

3/4

 

 

1

 

 

 

 

 

 

 

Blower Wheel Size (Dia x W) (in.)

 

8 x 7

 

 

 

9 x 7

 

 

9 x 8

 

 

10 x 10

 

 

11 x 10

WATER CONNECTION SIZE IPT (in.)

 

1/2

 

 

 

 

 

 

3/4

 

 

 

 

 

1

HORIZONTAL

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Air Coil Dimensions (H x W)(in.)

 

 

 

 

16 x 22

 

 

 

 

 

20 x 25

 

 

20 x 35

 

 

 

 

 

 

 

 

 

 

 

Standard Filter - (Qty) 1 in. Throwaway

 

 

 

(1) 16 x 25

 

 

 

 

 

(1) 20 x 28 or

 

(1) 20 x 24,

Weight (lb)

 

 

 

 

 

 

 

 

 

 

 

 

(2) 20 x 14

 

(1) 20 x 14

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Operating

153

 

 

158

 

 

189

 

 

197

 

 

203

 

 

218

 

263

 

 

303

 

 

 

 

 

Packaged

158

 

 

163

 

 

194

 

 

202

 

 

209

 

 

224

 

270

 

 

310

Corner Weight (lb)*

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Left-Front

53

 

 

55

 

 

62

 

 

67

 

 

75

 

 

81

 

98

 

 

103

Right-Front

36

 

 

37

 

 

40

 

 

41

 

 

47

 

 

50

 

60

 

 

64

Left-Back

34

 

 

35

 

 

39

 

 

40

 

 

44

 

 

48

 

58

 

 

61

Right-Back

30

 

 

31

 

 

33

 

 

34

 

 

37

 

 

39

 

47

 

 

75

VERTICAL

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Air Coil Dimensions (H x W)(in.)

 

 

 

20 x 17.25

 

 

 

 

 

24 x 17.75

 

24 x 28.25

 

 

 

 

 

 

 

 

 

Standard Filter - (Qty) 1 in. Throwaway

 

 

 

(1) 20 x 20

 

 

 

 

 

(1) 24 x 24

 

(1) 14 x 28, (1) 18 x 24

Weight (lb)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Operating

153

 

 

158

 

 

189

 

 

197

 

 

203

 

 

218

 

263

 

 

278

 

 

 

 

 

Packaged

158

 

 

163

 

 

194

 

 

202

 

 

209

 

 

224

 

270

 

 

285

LEGEND

 

 

 

 

 

 

*Front is located at control box end.

 

 

 

 

 

 

IPT — Internal Pipe Thread

 

 

 

 

 

 

NOTES:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1.

All units have grommet compressor mountings, and 1/2-in. and

PSC — Permanent Split Capacitor

 

 

 

 

 

 

 

 

 

 

 

 

3/4-in. electrical knockouts.

 

 

 

 

 

 

2. Maximum water working pressure is 500 psig.

3

Page 3
Image 3
Carrier PCV015-060 specifications 50PCH,PCV Unit Physical Data