Carrier PCV015-060 specifications a50-8440, Deluxe D

Models: PCV015-060

1 52
Download 52 pages 34.31 Kb
Page 15
Image 15
a50-8440

a50-8440

Deluxe D

15

 

 

 

LEGEND

AL

Alarm Relay Contacts

P1

Field Wiring Terminal Block

BM

Blower Motor

RVS

Reversing Valve Solenoid

BMC

Blower Motor Capacitor

TRANS

Transformer

BR

Blower Relay

TXV

Thermostatic Expansion Valve

CAP

Compressor Capacitor

 

 

 

 

 

 

 

 

 

 

Field Line Voltage Wiring

CB

Circuit Breaker

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Field Low Voltage Wiring

CC

Compressor Contactor

 

 

 

 

 

 

 

 

 

 

CO

Sensor, Condensate Overflow

 

 

 

 

 

 

 

 

 

 

Printed Circuit Trace

FP1

Sensor, Low Temperature Protection, Water Coil

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Optional Wiring

FP2

Sensor, Low Temperature Protection, Air Coil

 

 

 

 

 

 

 

 

 

 

HP

High-Pressure Switch

 

 

 

 

 

 

 

 

 

 

Relay/Contactor Coil

HPWS

High-Pressure Water Switch

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

JW1

Clippable Field Selection Jumper

 

 

 

 

 

 

 

 

 

 

 

LOC

Loss of Charge Pressure Switch

 

 

 

 

 

 

 

 

 

 

Condensate Pan

 

 

 

 

 

 

 

 

 

 

LON

Local Operating Network

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MV

Motorized Valve

 

 

 

 

 

 

 

 

 

 

Solenoid Coil

MVES

Motorized Valve End Switch

 

 

 

 

 

 

 

 

 

 

 

NEC

National Electrical Code

 

 

 

 

 

 

 

 

 

 

Temperature Switch

*Optional Wiring.

Thermistor

Ground

Wire Nut

Relay Contacts - N.C.

Relay Contacts - N.O.

Low Pressure Switch

High Pressure Switch

Splice Cap

Circuit Breaker

NOTES:

1.Compressor and blower motor thermally protected internally.

2.All wiring to the unit must comply with NEC and local codes.

3.Transformer is wired to 460-v BLK/RED lead for 460-3-60 units. Trans- former is energy limiting or may have circuit breaker.

4.FP1 thermistor provides low temperature protection for water. When using antifreeze solutions, cut JW3 jumper.

5.Refer to microprocessor control, LON, thermostat installation instruc- tions for wiring to the unit. Wire “N01” from LON to “Y1” Deluxe D when motorized valve is not used. Thermostat wiring must be Class 1 and voltage rating equal to or greater than unit supply voltage.

6.Factory cut JW4 jumper. Dry contact will be available between AL1 and AL2.

7.Transformer secondary ground via green wire with yellow stripe from “C” terminal to control box.

8.Blower motor is factory wired for medium and high speeds. For any other combination of speeds, attach black wire to the higher of the two desired speed taps at the motor, and attach the blue wire to the lower of the two desired speed taps.

9.Blower motor is factory wired for high and low speeds. No other combi- nation is available.

10.Optional LON wires. Only connect if LON connection is desired at the wall sensor.

11.The 460-v units using an internal secondary pump will require a neutral wire from the supply side in order to feed the accessory with 265-v.

Fig. 17 — 50PCH,PCV units with Deluxe D and LON Controller (460 V)

Page 15
Image 15
Carrier PCV015-060 specifications a50-8440, Deluxe D