Carrier PCV015-060 Wire Field Controls, Typical Deluxe D Control, Accessory Wiring, a50-8441

Models: PCV015-060

1 52
Download 52 pages 34.31 Kb
Page 22
Image 22
Step 9 — Wire Field Controls

Step 9 — Wire Field Controls

THERMOSTAT CONNECTIONS — The thermostat should be wired directly to the Aquazone™ control board. See Fig. 13-22, and 24.

COMPRESSOR CONTACTOR

CAPACITOR

COMPLETE C CONTROL

 

 

TERMINAL STRIP P2

C

TYPICAL

24 VAC WATER VALVE

LINE

LOAD

 

TRANSFORMER

a50-8197

Fig. 26 — Typical Deluxe D ControlAccessory WiringFig. 24 — Low Voltage Field WiringFig. 25 — Typical Aquazone Control Board J1

Y

W

R

S1

 

 

CFM

 

 

 

SW1

 

O

 

SW2

 

G

SW3

 

 

 

SW4

 

 

 

SW5

 

Y2

G

SW6

 

SW7

 

 

 

 

 

 

SW8

 

Y1

G

SW9

 

OFF

ON

 

 

G

G

G DEHUM

 

 

TB1

 

 

 

 

 

 

R

C

Y2 Y1 G

O

W

C

R DH AL1 A

A

AL1

A

Fig. 26 — Typical Deluxe D Control

Accessory Wiring

WATER SOLENOID VALVES — An external solenoid valve(s) should be used on ground water installations to shut off flow to the unit when the compressor is not operating. A slow closing valve may be required to help reduce water

THERMOSTAT CONNECTION

NOTE: Low voltage connector may be removed for easy installation.

Fig. 24 — Low Voltage Field Wiring

WATER FREEZE PROTECTION — The Aquazone control allows the field selection of source fluid freeze protection points through jumpers. The factory setting of jumper JW3 (FP1) is set for water at 30 F. In earth loop applications, jumper JW3 should be clipped to change the setting to 10 F when using antifreeze in colder earth loop applications. See Fig. 25.

a50-6268tf.tif

Fig. 25 — Typical Aquazone Control Board

Jumper Locations (Complete C Control Shown)

AIR COIL FREEZE PROTECTION — The air coil freeze protection jumper JW2 (FP2) is factory set for 30 F and should not need adjusting.

ACCESSORY CONNECTIONS — Terminal A on the control is provided to control accessory devices such as water valves, electronic air cleaners, humidifiers, etc. This signal operates with the compressor terminal. See Fig. 26. Refer to the specific unit wiring schematic for details.

NOTE: The A terminal should only be used with 24 volt signals — not line voltage signals.

hammer. Figure 26 shows typical wiring for a 24-vac external solenoid valve. Figures 27 and 28 illustrate typical slow closing water control valve wiring for Taco 500 Series and Taco ESP Series valves. Slow closing valves take approximately 60 sec. to open (very little water will flow before 45 sec.). Once fully open, an end switch allows the compressor to be energized (only on valves with end switches). Only relay or triac based electronic thermostats should be used with slow closing valves. When wired as shown, the slow closing valve will operate properly with the following notations:

1.The valve will remain open during a unit lockout.

2.The valve will draw approximately 25 to 35 VA through the “Y” signal of the thermostat.

IMPORTANT: Connecting a water solenoid valve can overheat the anticipators of electromechanical thermo- stats. Only use relay based electronic thermostats.

C

Y1

a50-8441

 

2

AMV

1

3

TACO VALVE

 

HEATER SWITCH

 

C

Y1

 

THERMOSTAT

 

Fig. 27 — AMV Valve Wiring

a50-8442

Fig. 28 — Taco SBV Valve Wiring

22

Page 22
Image 22
Carrier PCV015-060 Wire Field Controls, Typical Deluxe D Control, Accessory Wiring, Low Voltage Field Wiring, a50-8441