Carrier PCV015-060 specifications Unit Start-UpCooling Mode, Operating Limits - 50PCH,PCV Units

Models: PCV015-060

1 52
Download 52 pages 34.31 Kb
Page 28
Image 28

Table 14 — Operating Limits — 50PCH,PCV Units

AIR LIMITS

50PCH,PCV

Cooling (F)

Heating (F)

 

Min. Ambient Air – db

45

39

Rated Ambient Air – db

80.6

68

Max. Ambient Air – db

110

85

Min. Entering Air – db/wb

50

40

Rated Entering Air – db/wb

80.6/66.2

68

Max. Entering Air – db/wb

110/83

80

WATER LIMITS

 

 

Min. Entering Water

30

20

Normal Entering Water

50-110

30-70

Max. Entering Water

120

90

Normal Water Flow

2.5-3.0 gpm per ton

LEGEND

 

 

db — Dry Bulb wb — Wet Bulb

Scroll Compressor Rotation — It is important to be certain compressor is rotating in the proper direction. To determine whether or not compressor is rotating in the prop- er direction:

1.Connect service gages to suction and discharge pressure fittings.

2.Energize the compressor.

3.The suction pressure should drop and the discharge pressure should rise, as is normal on any start-up.

If the suction pressure does not drop and the discharge pressure does not rise to normal levels:

1.Turn off power to the unit. Install disconnect tag.

2.Reverse any two of the unit power leads.

3.Reapply power to the unit and verify pressures are correct.

The suction and discharge pressure levels should now move to their normal start-up levels.

When the compressor is rotating in the wrong direction, the unit makes more noise and does not provide cooling.

After a few minutes of reverse operation, the scroll com- pressor internal overload protection will open, thus activating the unit lockout. This requires a manual reset. To reset, turn the thermostat on and then off.

NOTE: There is a 5-minute time delay before the compressor will start.

Unit Start-Up Cooling Mode

1.Adjust the unit thermostat to the warmest position. Slowly reduce the thermostat position until the compres- sor activates.

2.Check for cool air delivery at unit grille a few minutes after the unit has begun to operate.

3.Verify that the compressor is on and that the water flow rate is correct by measuring pressure drop through the heat exchanger using P/T plugs. See Table 15. Check the elevation and cleanliness of the condensate lines; any dripping could be a sign of a blocked line. Be sure the condensate trap includes a water seal.

4.Check the temperature of both supply and discharge wa- ter. Compare to Tables 16-22. If temperature is within range, proceed. If temperature is outside the range, check the cooling refrigerant pressures in Tables 16-22.

5.Check air temperature drop across the coil when com- pressor is operating. Air temperature drop should be between 15 and 25 F.

Table 15 — Water Temperature Change

Through Heat Exchanger

 

COOLING

HEATING

WATER FLOW RATE (GPM)

RISE (F)

DROP (F)

 

Min

Max

Min

Max

For Closed Loop: Ground Source or

9

12

4

8

Cooling/Boiler Systems at 3 gpm/ton

 

 

 

 

For Open Loop: Ground Water Systems at

20

26

10

17

1.5 gpm/ton

 

 

 

 

Table 16 — 50PC015,018 Typical Unit Operating Pressures and Temperatures

ENTERING

 

 

 

COOLING

 

 

 

 

 

HEATING

 

 

 

 

 

WATER

WATER

Suction

Discharge

Super-

Sub-

Water

Air Temp

Suction

Discharge

Super-

Sub-

Water

Air Temp

 

FLOW

 

TEMP

Pressure

Pressure

heat

cooling

Temp

Drop

Pressure

Pressure

heat

cooling

Temp

Rise

 

(F)

(GPM/ton)

Rise

Drop

 

 

(psig)

(psig)

(F)

(F)

(F)

(F) DB

(psig)

(psig)

(F)

(F)

 

(F)

 

(F) DB

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1.5

120-130

155-175

27-32

11-16

16.9-19.9

16-22

73-

83

268-288

8-13

4-

9

6.1-

8.1

15-21

 

30

2.25

120-130

142-162

27-32

9-14

12.5-14.5

17-23

75-

85

270-290

8-13

4-

9

4.4-

6.4

16-22

 

 

3

120-130

128-148

27-32

9-14

8.1-10.1

17-23

78-

88

272-292

8-13

4-

9

2.9-

4.9

16-22

 

 

1.5

137-147

220-240

16-21

10-15

17.0-19.0

16-22

102-112

295-315

8-13

8-13

9.1-11.1

20-26

 

50

2.25

137-147

206-226

16-21

8-13

12.6-14.6

17-23

106-116

297-317

8-13

8-13

6.9-

8.9

21-27

 

 

3

137-147

192-212

16-21

8-13

8.4-10.4

17-23

110-120

299-319

8-13

8-13

4.7-

6.7

21-27

 

 

1.5

142-152

287-307

7-12

10-15

15.9-17.9

16-22

131-141

324-344

9-14

10-15

12.1-14.1

25-33

 

70

2.25

142-152

273-239

7-12

8-13

11.8-13.8

17-23

137-147

326-346

9-14

10-15

9.3-11.3

26-34

 

 

3

142-152

259-279

7-12

8-13

7.8- 9.8

17-23

144-154

328-348

9-14

10-15

6.6-

8.6

26-34

 

 

1.5

146-156

375-395

6-11

10-15

14.9-16.9

16-22

174-184

360-380

10-15

12-17

15.8-17.8

32-40

 

90

2.25

146-156

361-381

6-11

8-13

11.0-13.0

17-23

180-190

367-387

11-16

12-17

11.9-13.9

33-41

 

 

3

146-156

347-367

6-11

8-13

7.2- 9.2

17-23

187-197

374-394

12-17

12-17

8.0-10.0

33-41

 

110

1.5

154-164

478-498

6-11

10-15

14.0-16.0

16-22

 

 

 

 

2.25

154-164

461-481

6-11

8-13

10.2-12.2

16-22

 

 

 

 

 

3

154-164

445-465

6-11

8-13

6.5- 8.5

16-22

 

 

 

 

 

LEGEND

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DB

Dry Bulb

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

No Heating Operation in This Temperature Range

 

 

 

 

 

 

 

 

 

 

 

 

28

Page 28
Image 28
Carrier PCV015-060 specifications Unit Start-UpCooling Mode, Operating Limits - 50PCH,PCV Units, Water Temperature Change