Carrier PCV015-060 specifications Deluxe D

Models: PCV015-060

1 52
Download 52 pages 34.31 Kb
Page 13
Image 13
Deluxe D

13

AL

Alarm Relay Contacts

BM

Blower Motor

BMC

Blower Motor Capacitor

BR

Blower Relay

CAP

Compressor Capacitor

CB

Circuit Breaker

CCCompressor Contactor

CO

Sensor, Condensate Overflow

FP1

Sensor, Low Temperature Protection Water Coil

FP2

Sensor, Low Temperature Protection Air Coil

HP

High-Pressure Switch

HPWS

High-Pressure Water Switch

JW1

Clippable Field Selection Jumper

*Optional.

 

Deluxe D

LEGEND

LOC

Loss of Charge Pressure Switch

MV

Motorized Valve

MVES

Motorized Valve End Switch

NEC

National Electrical Code

P1

Field Wiring Terminal Block

PB

Power Block

RVS

Reversing Valve Solenoid

TRANS

Transformer

TXV

Thermostatic Expansion Valve

 

Field Line Voltage Wiring

 

Field Low Voltage Wiring

 

Printed Circuit Trace

 

Optional Wiring

Relay/Contactor Coil

Condensate Pan

Solenoid Coil

Thermistor

Ground

Wire Nut

NOTES:

1.Compressor thermally protected internally.

2.All wiring to the unit must comply with NEC and local codes.

3.Transformer is wired to 460-v BLK/RED lead for 460-3-60 units or 575-v GRY lead for 575-3-60 units. Transformer is energy limiting or may have circuit breaker.

4.FP1 thermistor provides low temperature protection for water. When using antifreeze solutions, cut JW3 jumper.

5.Refer to microprocessor control, LON, or thermostat installation instruc- tions for wiring to the unit. Wire “Y” from thermostat to “Y1” Deluxe D when motorized valve is not used. Thermostat wiring must be Class 1 and voltage rating equal to or greater than unit supply voltage. Heat/cool thermostats not compatible with motorized water valve.

6.24-v alarm signal shown. For dry alarm contact, cut JW4 jumper and dry contact will be available between AL1 and AL2.

7.Transformer secondary ground via green wire with yellow stripe from “C” terminal to control box.

8.Blower motor is factory wired for medium and high speeds. For any other combination of speeds, attach black wire to the higher of the two desired speed taps at the motor. Attach the blue wire to the lower of the two desired speed taps.

9.Blower motor is factory wired for high and low speeds. No other combi- nation of speeds is available.

10.The 460-v units using an internal secondary pump will require a neutral wire from the supply side in order to feed the accessory with 265-v.

Fig. 15 — 50PCH,PCV Units with Deluxe D Controller, Three-Phase (460 V)

Page 13
Image 13
Carrier PCV015-060 specifications Deluxe D