Carrier PCV015-060 specifications Deluxe D

Models: PCV015-060

1 52
Download 52 pages 34.31 Kb
Page 12
Image 12
Deluxe D

12

AL

Alarm Relay Contacts

BM

Blower Motor

BMC

Blower Motor Capacitor

CAP

Compressor Capacitor

CB

Circuit Breaker

CCCompressor Contactor

CO

Sensor, Condensate Overflow

FP1

Sensor, Low Temperature Protection Water Coil

FP2

Sensor, Low Temperature Protection Air Coil

HP

High-Pressure Switch

HPWS — High-Pressure Water Switch

HWTS — High Leaving Water Temperature Switch

JW1

Jumper, Alarm

*Optional.

Deluxe D

LEGEND

LOC

Loss of Charge Pressure Switch

MV

Motorized Valve

MVES

Motorized Valve End Switch

NEC

National Electrical Code

P1

Field Wiring Terminal Block

RVS

Reversing Valve Solenoid

TRANS

Transformer

TXV

Thermostatic Expansion Valve

Field Line Voltage Wiring

Field Low Voltage Wiring

Printed Circuit Trace

Optional Wiring

Relay/Contactor Coil

Condensate Pan

Solenoid Coil

Thermistor

Ground

Wire Nut

NOTES:

1.Compressor thermally protected internally.

2.All wiring to the unit must comply with NEC and local codes.

3.Transformer is wired to 208-v RED lead for 208-3-60 units. For 230-3-60, switch RED and ORG leads at L1 and insulate RED lead. Transformer is energy limiting or may have circuit breaker.

4.FP1 thermistor provides freeze protection for water. When using anti- freeze solutions, cut JW3 jumper.

5.Refer to microprocessor control, LON, or thermostat installation instruc- tions for wiring to the unit. Wire “Y” from thermostat to “Y1” Deluxe D

when motorized valve is not used. Thermostat wiring must be Class 1 and voltage rating equal to or greater than unit supply voltage. Heat/cool thermostats not compatible with motorized water valve.

6.24-v alarm signal shown. For dry alarm contact, cut JW4 jumper and dry contact will be available between AL1 and AL2.

7.Transformer secondary ground via green wire with yellow stripe from “C” terminal to control box.

8.Blower motor is factory wired for medium and high speeds. For any other combination of speeds, attach black wire to the higher of the two desired speed taps and the blue wire to the lower of the two desired speed taps.

Fig. 14 — 50PCH,PCV Units with Deluxe D Controller, Three-Phase (208/230 V)

Page 12
Image 12
Carrier PCV015-060 specifications Deluxe D