Table 3 — 50PCH,PCV Unit Electrical Data
50PCH,PCV | VOLTAGE | RATED | VOLTAGE | COMPRESSOR |
| STANDARD UNITS |
| UNITS WITH HIGH STATIC BLOWER | |||||||||
UNIT SIZE | CODE | VOLTAGE | MIN/MAX | QTY | RLA | LRA | Fan Motor |
| Total Unit | MCA | Max Fuse/ | Fan Motor | Total Unit | MCA | Max Fuse/ | ||
| |||||||||||||||||
|
|
|
|
|
|
| FLA |
|
| FLA |
| HACR | FLA | FLA |
| HACR | |
015 |
| 3 | 197/254 | 1 | 6.0 | 29.0 | 1.00 |
|
| 7.0 | 8.5 | 15 | 1.00 | 1.00 | 7.0 | 15 | |
| 4 | 239/292 | 1 | 5.4 | 28.0 | 0.86 |
|
| 6.3 | 7.6 | 15 | 0.86 | 0.86 | 6.3 | 15 | ||
|
|
|
| ||||||||||||||
018 |
| 3 | 197/254 | 1 | 7.2 | 33.0 | 1.00 |
|
| 8.2 | 10.0 | 15 | 1.50 | 1.50 | 8.7 | 15 | |
| 4 | 239/292 | 1 | 5.9 | 28.0 | 0.86 |
|
| 6.8 | 8.2 | 15 | 1.30 | 1.30 | 7.2 | 15 | ||
|
|
|
| ||||||||||||||
024 |
| 3 | 197/254 | 1 | 12.8 | 58.3 | 1.50 |
|
| 14.3 | 17.5 | 30 | 3.00 | 3.00 | 15.8 | 30 | |
| 4 | 239/292 | 1 | 9.6 | 54.0 | 1.30 |
|
| 10.9 | 13.3 | 20 | 2.70 | 2.70 | 12.3 | 20 | ||
|
|
|
| ||||||||||||||
|
| 3 | 197/254 | 1 | 14.1 | 73.0 | 3.00 |
|
| 17.1 | 20.6 | 30 | 3.00 | 3.00 | 17.1 | 30 | |
030 |
| 4 | 239/292 | 1 | 11.2 | 60.0 | 2.70 |
|
| 13.9 | 16.7 | 25 | 2.70 | 2.70 | 13.9 | 25 | |
| 5 | 197/254 | 1 | 8.9 | 58.0 | 3.00 |
|
| 11.9 | 14.1 | 20 | 3.00 | 3.00 | 11.9 | 20 | ||
|
|
|
| ||||||||||||||
|
| 6 | 414/506 | 1 | 4.2 | 28.0 | 1.70 |
|
| 5.9 | 7.0 | 15 | 1.70 | 1.70 | 5.9 | 15 | |
|
| 3 | 197/254 | 1 | 16.7 | 79.0 | 1.80 |
|
| 18.5 | 22.7 | 35 | 3.00 | 3.00 | 19.7 | 40 | |
036 |
| 4 | 239/292 | 1 | 13.5 | 72.0 | 2.00 |
|
| 15.5 | 18.9 | 30 | 2.70 | 2.70 | 16.2 | 30 | |
| 5 | 197/254 | 1 | 10.4 | 73.0 | 1.80 |
|
| 12.2 | 14.8 | 25 | 3.00 | 3.00 | 13.4 | 25 | ||
|
|
|
| ||||||||||||||
|
| 6 | 414/506 | 1 | 5.8 | 38.0 | 1.24 |
|
| 7.0 | 8.5 | 15 | 1.70 | 1.70 | 7.5 | 15 | |
|
| 3 | 197/254 | 1 | 17.9 | 112.0 | 3.00 |
|
| 20.9 | 25.4 | 40 | 3.00 | 3.00 | 20.9 | 40 | |
042 |
| 5 | 197/254 | 1 | 13.5 | 88.0 | 3.00 |
|
| 16.5 | 19.9 | 30 | 3.00 | 3.00 | 16.5 | 30 | |
| 6 | 414/506 | 1 | 6.0 | 44.0 | 1.70 |
|
| 7.7 | 9.2 | 15 | 1.70 | 1.70 | 7.7 | 15 | ||
|
|
|
| ||||||||||||||
|
| 1 | 518/633 | 1 | 4.9 | 34.0 | 1.40 |
|
| 6.3 | 7.5 | 15 | 1.40 | 1.40 | 6.3 | 15 | |
|
| 3 | 197/254 | 1 | 21.8 | 117.0 | 3.40 |
|
| 25.2 | 30.7 | 50 | 4.90 | 4.90 | 26.7 | 50 | |
048 |
| 5 | 197/254 | 1 | 13.7 | 83.1 | 3.40 |
|
| 17.1 | 20.5 | 30 | 4.90 | 4.90 | 18.6 | 35 | |
| 6 | 414/506 | 1 | 6.2 | 41.0 | 1.80 |
|
| 8.0 | 9.6 | 15 | 2.50 | 2.50 | 8.7 | 15 | ||
|
|
|
| ||||||||||||||
|
| 1 | 518/633 | 1 | 4.8 | 33.0 | 1.40 |
|
| 6.2 | 7.4 | 15 | 1.90 | 1.90 | 6.7 | 15 | |
|
| 3 | 197/254 | 1 | 26.3 | 134.0 | 4.90 |
|
| 31.2 | 37.8 | 60 | 5.80 | 5.80 | 32.1 | 60 | |
060 |
| 5 | 197/254 | 1 | 15.6 | 110.0 | 4.90 |
|
| 20.5 | 24.4 | 40 | 5.80 | 5.80 | 21.4 | 40 | |
| 6 | 414/506 | 1 | 7.8 | 52.0 | 2.50 |
|
| 10.3 | 12.3 | 20 | 2.60 | 2.60 | 10.4 | 20 | ||
|
|
|
| ||||||||||||||
|
| 1 | 518/633 | 1 | 5.8 | 38.9 | 1.90 |
|
| 7.7 | 9.2 | 15 | 2.30 | 2.30 | 8.1 | 15 | |
|
| LEGEND |
|
|
|
|
| *Units using | |||||||||
FLA | — | Full Load Amps |
|
|
|
|
| HWR (hot water reheat), and/or internal secondary pump will require a neutral | |||||||||
|
|
|
|
| wire from the supply side in order to feed accessory with |
| |||||||||||
HACR | — Heating, Air Conditioning and Refrigeration |
|
|
|
| ||||||||||||
|
|
| NOTES: |
|
|
|
|
|
| ||||||||
LRA | — | Locked Rotor Amps |
|
|
|
|
|
|
|
|
|
|
| ||||
MCA | — | Minimum Circuit Amps |
|
|
|
|
|
| 1. HACR circuit breaker in U.S.A. only. |
|
|
| |||||
RLA | — | Rated Load Amps |
|
|
|
|
| 2. | All fuses |
|
|
|
|
| |||
|
|
|
|
|
|
|
|
| 3. | Class |
|
|
|
|
|
a50-8162
Fig. 23 — Typical
21