Trouble

 

Probable Cause

 

Remedy

COMPRESSOR DOES NOT

J.

Inoperable control board

J.

Replace control board.

OPERATE (con’t).

 

 

 

 

 

K.

Inoperable contactor

K.

Replace contactor.

 

L.

No voltage to control board.

L. Check for loose or broken wiring.

 

 

 

 

Check 240/24 VAC power

 

 

 

 

transformer for 24 VAC output.

 

 

 

 

(see NOTE below).

 

M.

Inoperable control board or

M.

Replace control board.

 

 

water/ice sensor PC board.

 

 

 

N.

Inoperable ICE SENSOR.

N.

Replace ICE SENSOR.

 

O.

EVAP IN, COND OUT, or

O.

Replace inoperable sensor.

 

 

EVAP OUT sensor is open,

 

 

 

 

shorted, or out of temperature

 

 

 

 

range.

 

 

P.Hydro Boostâ WATER SENSOR is shorted or open circuit.

P.Check for loose, broken, or disconnected wire or plug at pre-cool coil. Repair or replace wire or secure plug. If Hydro Boostâ WATER SENSOR is inoperable, replace sensor.

NOTE: Confirm which sensor has failed by using the Aurora Series System Analyzer (P/N 309197-000).

NOTE: The 240/24 VAC power transformer has an overload reset button located on its 24 VAC output side (see Figure 3). An overload on the transformer will cause its reset button to pop out disrupting the 24 VAC output to the main control board. Overload button must be pressed in to restore 24 VAC output.

COMPRESSOR OPERATES

A. Cooling capacity is exceeded

CONTINUOUSLY BUT DOES

by overdrawing.

NOT FORM SUFFICIENT ICE

 

BANK

 

A.Reduce amount of drinks drawn per given time.

B. Air circulation through Remote

B. Check and if necessary, clean

Condenser Coil and Fan

condenser coil as instructed.

Assembly Condenser Coil is

 

restricted.

 

C.Insufficient refrigerant charge. C. Check Cooling Unit sight glass for bubbles or liquid break. Find and repair refrigeration leak, the replenish refrigerant charge.

D.Inoperative or disconnected pulse-modulating expansion valve (see REFRIGERATION FLOW DIAGRAM).

D.Check that expansion valve is operating by touch (should be able to feel valve pulse).

Check for loose or disconnected wire to solenoid coil. If necessary, troubleshoot expansion valve with a gage set to see if it is opening. If expansion valve is not opening, suction pressure will be in a vacuum.

300614000

34

Page 38
Image 38
Cornelius 10, 000 PLUS installation manual Compressor Operates, Continuously but does, Not Form Sufficient ICE Bank

000 PLUS, 10 specifications

Cornelius 10,000 PLUS is a pioneering innovation in the beverage dispensing industry, designed to cater to the evolving needs of commercial establishments. This advanced system combines state-of-the-art technology with user-friendly features, making it a standout choice for restaurants, cafes, and bars aiming to enhance their beverage service.

One of the main features of the Cornelius 10,000 PLUS is its impressive capacity. With the ability to dispense a wide variety of beverages, including soft drinks, cocktails, and craft beers, the system supports a large volume of service, perfect for high-demand environments. The modular design allows for easy expansion, enabling businesses to add additional flavors or beverages as needed without major overhauls.

The technology behind the Cornelius 10,000 PLUS is equally impressive. It utilizes advanced cooling technology to ensure that beverages are served at the optimal temperature, enhancing the customer experience. The integrated touchless dispensing mechanism minimizes waste and ensures a hygienic experience, addressing growing concerns about cleanliness in food service environments. This technology also improves speed, allowing staff to serve customers more efficiently.

Another key characteristic of the Cornelius 10,000 PLUS is its digital integration capabilities. The system can be connected to a central management platform that tracks sales, inventory levels, and maintenance needs in real-time. This allows operators to optimize their beverage offerings based on customer preferences and reduces downtime through proactive maintenance alerts.

In addition to its performance features, the Cornelius 10,000 PLUS is designed with sustainability in mind. The system employs energy-efficient practices, reducing its environmental footprint while lowering operational costs. The materials used in construction are durable yet eco-friendly, ensuring longevity and less waste.

Overall, the Cornelius 10,000 PLUS stands out as an essential tool for any business looking to elevate its beverage service. With its combination of high capacity, cutting-edge technology, and sustainability features, it not only meets the demands of today’s fast-paced service environments but also positions establishments for future growth and success.